•  All other vent orientations 
(horizontal, 45°, ect) must be 
supported with a Wallstrap at 
every joint within 6in (150mm) of 
the female end. Maximum space 
between Wallstraps is 3.25ft (1m).
•  Elbows and Tees must be supported 
by a Wallstrap within 4in (100mm) 
after the Elbow or Tee section.
(Fig.22)
•  3/8"-16 or greater all-thread rod 
may be used as an extension with 
DuraVent Wallstraps.
5.  Concentric Polypro adjustable vent pipe 
must be secured with the provided sheet 
metal screws at the sliding joint as well as 
at the male and female ends of the vent 
pipe. Adjustable sections can extend from 
a minimum of 11in (280mm) length to a 
maximum of 15.5in (393mm) length. 
6.  Polypro Concentric can be insulated in 
unconditioned space or when run outside. 
Use mineral wool or housing insulation.
TERMINATIONS
Horizontal Concentric Pipe (Fig.23)
1.  Locate the penetration in the wall. Measure 
the intended path of the installation and 
make sure you have all the necessary vent 
lengths and components to complete the 
install. 
2.  Cut and frame the penetration following 
the dimensions in Table 3. 
3.  Center the Interior Wall Thimble Plate to the 
wall penetration and secure with the four 
provided screws. 
(Fig.23)
4.  Attach the Exterior Wall Thimble Plate to 
the Horizontal Vent Termination. Insert 
the assembly through the Interior Wall 
Plate from the exterior of the building. 
If necessary, cut the male end of the 
termination to the length needed for the 
install.
5.  Center the Exterior Wall Plate to the wall 
penetration, use water resistant sealant or 
caulking on the exterior plate to prevent 
APPLY BEAD OF 
SILICON SEALANT
EXTERIOR WALL
THIMBLE PLATE
INTERIOR WALL
THIMBLE PLATE
Figure 23
rain intrusion. Secure the Exterior Wall 
Plate in place using the provided screws. 
(Fig.23)
6.  Vent termination should be installed ush 
against the Exterior Wall Plate. Orient the 
termination so the air intake slots face 
downward to prevent rain intrusion. Secure 
the termination orientation using screws at 
the joint connection. 
7.  Seal the gap between the termination and 
wall thimble, exposed screw heads, and the 
edges of the exterior wall thimble plate 
with water resistant sealant or caulking. 
8.  Assemble any remaining sections between 
the termination and the appliance. 
•  If using a PolyPro Single-Wall to 
PolyPro Concentric adapter, install 
gaskets as shown in Fig.24 before 
connecting to the vent pipe.
•  Assemble the PolyPro Single-Wall 
venting according to the DuraVent 
PolyPro Single-Wall instructions 
beginning on page 7.