Install Instructions
5
IMPORTANT
To prevent possible recirculation of ue 
gases, the installer must consider the 
eects of prevailing wind conditions, eddy 
zones, nearby buildings, obstructions, 
or other obstacles such as shrubs when 
planning exhaust and air intake locations.  
DuraVent can not be held responsible for 
poor appliance performance or damage to 
buildings due to an incorrect installation. 
The minimum clearances detailed within 
our instructions may not be adequate in 
some circumstances depending on the 
specics of the installation. For this reason 
we always recommend vertical venting.
Refer to the appliance manufacturer's 
instructions for maximum and minimum 
vent lengths permitted with your specic 
appliance model. This information should 
include guidance on the maximum number 
of elbows and related pressure-drops. The 
total vent length from the appliance to 
the termination shall not be greater than 
specied by the appliance manufacturer. 
If specic guidance is not oered by the 
appliance manufacturer as to Equivalent 
Vent Lengths (EVL) for vent components, the 
general guidelines in Table 2 can be used.
CONDENSATE DRAIN (Fig.1)
Refer to the appliance manufacturer’s 
installation instructions for requirements of 
condensate drainage. Ensure proper system 
slope for drainage. (Fig.7 and 20)
When using a P-Trap style drain, connect 
1-1/4in (32mm) tubing and secure into a 
loop. Fill the loop partially with water to 
prevent exhaust leakage. Route the free end 
of the loop to an appropriate disposal. 
Figure 1
SIPHON
Table 2 - Equivalent Length Chart
2" Equivalent 
Length
3" Equivalent 
Length
4" Equivalent 
Length
5" Equivalent 
Length
6" Equivalent 
Length
8" Equivalent 
Length
1-ft Vent Pipe 1-ft 1-ft 1-ft 1-ft 1-ft 1-ft
1-ft Flex Pipe
(same diameter 
as rigid)
2-ft 2-ft 2-ft 2-ft N/A N/A
1-ft Flex Pipe
(up-sized one 
diameter)
0.4-ft  0.6-ft  0.6-ft  N/A N/A N/A
45 Elbow 3-ft 3-ft 5-ft 6-ft 6-ft 13-ft
90 Elbow 5-ft 7-ft 12-ft 14-ft 14-ft 19-ft
Tee 9-ft 12-ft 19-ft 21-ft 22-ft 29-ft
WARNING
CARBON MONOXIDE POISONING HAZARD 
Failure to follow these installation 
instructions could result in personal 
injury or death.
P-TRAP