Installation Guide
4
CLEARANCES AND APPLICATIONS
DuraVent’s PelletVent is listed by 
Underwriters Laboratories as a vent for 
listed oil-, pellet-, (multi-fuel) appliances. 
PelletVent is also listed as a masonry reliner, 
in which case the minimum clearance is 
0” from vent to masonry, and 0” clearance 
from the masonry to nearby combustibles. 
Never ll any required clearance space 
with insulation or any other materials 
(except insulation explicitly approved by 
DuraVent as noted below). Combustible 
materials include (but are not limited to) 
lumber, plywood,sheetrock, plaster and lath, 
furniture, curtains, electrical wiring, and 
building insulation except that noted below. 
The minimum clearance to combustibles 
from PelletVent is 1” for oil, pellet or other 
approved fuels. A major cause of vent 
related res is failure to maintain required 
clearances (air spaces) to combustible 
materials. It is of the utmost Importance 
that double wall pellet vent be installed 
only in accordance with these Instructions.
NONCOMBUSTIBLE INSULATION
DuraVent approves the eld application 
of non-combustilble insulation within the 
clearance to combustible distance (in wall 
thimbles or support boxes) if/when desirable.  
Approved insulation must be listed / 
compliant with ASTM E136/ULC S114 as Non-
Combustible, have a melting temperature 
above 2000°F/1100°C, be water resistant with 
low moisture absorbtion and be acceptable 
to the AHJ. Materials would include those 
made from stone (aka “rockwool” or “mineral 
wool” insulations). NOTE- Fiberglass 
insulation is NOT approved!
VENT LISTING
PelletVent is listed (MH8381 & MH14420) 
to UL 641 Type L Low Temperature Venting 
Systems, UL 1777 Relining, and ULC S609 Low 
Temperature Vents.
INSTALLATION NOTES
Proper planning for your PelletVent 
installation will result in greater safety, 
eciency, and convenience,saving both time 
and money. Use only authorized DuraVent 
PelletVent listed parts. Do not install 
damaged parts. 
1. WARNING: When passing through 
ceilings and walls, make sure all combustible 
materials and combustible building 
insulation products are a minimum of 1” from 
the vent pipe.
2. When exiting through walls, make sure 
NFPA rules are followed for distance from 
windows and openings. 
3. Do not mix and match with other products 
or improvise solutions.
4. Practice good workmanship. Sloppy work 
could jeopardize your installation.
5. Never use a vent with an inside diameter 
that is smaller than the appliance ue outlet.
6. Multistory: Where PelletVent passes 
through the ceiling, use an approved and 
listed Firestop/Support assembly.
7. PelletVent placement: When deciding 
the location of your stove and vent, try to 
minimize the alteration and reframing of 
structural components of the building.
8. Sections of pipe are connected to each 
other by pushing them rmly together and 
twisting. Screws are not required. If however, 
screws are desired, use 1/4”-long sheet metal 
screws. Under no circumstances penetrate 
the inner liner with screws.
9. 500 RTV Sealant may be required at all vent 
joints. Apply to inner female socket. Refer to 
Appliance manufacturer for further detail.
10. Never install single-wall pipe to 
freestanding pellet stoves. Single-wall pipe 
may be connected to a replace insert, 
provided it is inside the replace, and the 
replace has completely sealed surroundings.
11. Do not connect B-Vent pipe with 
aluminum liners to pellet appliances.
12. Inspections: Using pelletized fuel does 










