Product Manual

14
EXTENDED ROOF BRACKET
INSTALLATION
If the chimney extends more than 4 feet above
the rooine, an Extended Roof Bracket must
be installed at every 4-foot increment of height
above the rooine, leaving no more than 4 feet
extending above the last pipe band.
1. Mount Pipe Band: Slip the Pipe Band
around the chimney and secure by tightening
the nut and bolt.
2. Install Roof Brackets: Measure from the
Pipe Band to the points where the conduit will
meet the roof, and form approximately a 60°
angle with the chimney, and with each other.
(Figures 18 and 19). Cut 2 pieces of 3/4 inch
thin wall galvanized steel electrical conduit, (or
rigid galvanized tubing) to these lengths. The
conduit is not furnished by Simpson Dura-Vent,
and must be locally procured. Mount the two
Roof Brackets where the conduit meets the
roof, using 6 roong nails per bracket. Seal
the nail heads carefully with a non-hardening,
waterproof sealant.
3. Attach Conduit: Flatten 1 inch and drill
a 1/4-inch hole at each end of both pieces of
conduit. Bolt each conduit to the Pipe Band
and Roof Brackets with the nuts and bolts
provided.
Figure 20
A MINIMUM OF 2 INCHES
BELOW FINISHED CEILING
18 INCHES MINIMUM FOR
SINGLE-WALL STOVEPIPE
CAP
SDP-C
STORM COLLAR
SDP-SC
VENTILATED FLASHING
SDP-F
CHIMNEY SECTIONS
SDP-P
ROOF
FRAMED OPENING
SQUARE CEILING SUPPORT
BOX SDP-SB
PUSH SUPPORT BOX UP
THROUGH ROOF, TRIM
AND FOLD BACK EXCESS
AS SHOWN IN FIG. 22
Figure 18
EXTENDED
ROOF
BRACKET
SDP-RSA
CHIMNEY SECTION
SDP-P
3/4 INCH THIN-WALL
GALVANIZED ELECTRICAL
CONDUIT (NOT FURNISHED)
60º
Figure 19
CHIMNEY CAP SDP-C
EXTENDED ROOF BRACKET SDP-RSA
STORM COLLAR SDP-SC
FLASHING SDP-F,
SDP-TF
60º
CONSISTS OF: (1) PIPE BAND, (2) ROOF BRACKET CONNECTED
WITH 3/4 INCH THIN-WALL GALVANIZED ELECTRICAL CONDUIT. (NOT
FURNISHED BY SIMPSON DURA-VENT). FLATTEN ENDS AND BOLT TO
PIPE BAND AND BRACKET.
NOTE: IF
DIMENSION ‘A
IS GREATER
THAN 4-FEET,
EXTENDED
FOOF BRACKET
MUST BE USED.
A