Installation Guide
14
EXTENDED ROOF BRACKET 
INSTALLATION 
If the chimney extends more than 4 feet above 
the rooine, an Extended Roof Bracket must 
be installed at every 4-foot increment of height 
above the rooine, leaving no more than 4 feet 
extending above the last pipe band.
1. Mount Pipe Band: Slip the Pipe Band 
around the chimney and secure by tightening 
the nut and bolt. 
2. Install Roof Brackets: Measure from the 
Pipe Band to the points where the conduit will 
meet the roof, and form approximately a 60° 
angle with the chimney, and with each other. 
(Figures 18 and 19). Cut 2 pieces of 3/4 inch 
thin wall galvanized steel electrical conduit, 
(or rigid galvanized tubing) to these lengths. 
The conduit is not furnished by DuraVent, 
and must be locally procured. Mount the two 
Roof Brackets where the conduit meets the 
roof, using 6 roong nails per bracket. Seal 
the nail heads carefully with a non-hardening, 
waterproof sealant. 
3. Attach Conduit:  Flatten 1 inch and drill 
a 1/4-inch hole at each end of both pieces of 
conduit. Bolt each conduit to the Pipe Band 
and Roof Brackets with the nuts and bolts 
provided. 
Figure 20
A MINIMUM OF 2 INCHES 
BELOW FINISHED CEILING
18 INCHES MINIMUM FOR 
SINGLE-WALL STOVEPIPE
CAP
SDP-C
STORM COLLAR
SDP-SC
VENTILATED FLASHING
SDP-F
CHIMNEY SECTIONS
SDP-P
ROOF
FRAMED OPENING
SQUARE CEILING SUPPORT 
BOX SDP-SB
PUSH SUPPORT BOX UP 
THROUGH ROOF, TRIM 
AND FOLD BACK EXCESS 
AS SHOWN IN FIG. 22
Figure 18
EXTENDED 
ROOF 
BRACKET
SDP-RSA
CHIMNEY SECTION
SDP-P
3/4 INCH THIN-WALL 
GALVANIZED ELECTRICAL 
CONDUIT (NOT FURNISHED)
60º
Figure 19
CHIMNEY CAP SDP-C
EXTENDED ROOF BRACKET SDP-RSA
STORM COLLAR SDP-SC
FLASHING SDP-F, 
SDP-TF
60º
CONSISTS OF: (1) PIPE BAND, (2) ROOF BRACKET CONNECTED 
WITH 3/4 INCH THIN-WALL GALVANIZED ELECTRICAL CONDUIT. (NOT 
FURNISHED BY DURAVENT). FLATTEN ENDS AND BOLT TO PIPE BAND 
AND BRACKET.
NOTE: IF 
DIMENSION ‘A’ 
IS GREATER 
THAN 4-FEET, 
EXTENDED 
FOOF BRACKET 
MUST BE USED.
A