Installation Guide
19
in the event the chimney is to be enclosed. 
The other is a at plate, to be used in cases 
when the chimney is not enclosed. 
3. Attach Chimney: Place the rst Chimney 
Section over the ange on the Anchor Plate 
with the arrows pointing up. Drill 1/8-inch 
diameter holes through the outer sleeve of the 
Chimney Section which match the location of 
the corresponding holes in the Anchor Plate. 
Secure the Chimney Section to the Anchor 
Plate with #8 self-tapping sheet metal screws.  
4. Finish Chimney: Install the rest as directed 
in the Ceiling Supported Installation section, 
Steps 4 through 10. Refer to Figure 1 and 
Table 4 for chimney height requirements. 
Always maintain at least 2 inches of clearance 
to combustible materials, and enclose the 
chimney where it passes through occupied 
areas. Use a Wall Strap for every four feet of 
chimney height. 