Installation Guide
9
Table 2
Figure 10
Figure 8
FRAMING
FIRESTOP 
RADIATION SHIELD
Figure 9
TWIST CLOCKWISE 
TO TIGHTEN
ATTIC INSULATION 
SHIELD
Framing Dimensions
Chimney Diameter
5” 6” 7” 8”
CATHEDRAL CEILING 
SUPPORT BOX
111/4” 121/4” 131/4” 141/2”
FLAT CEILING 
SUPPORT BOX
111/4” 121/4” 131/4” 141/2”
ROUND CEILING 
SUPPORT BOX
111/4” 121/4” 131/4” 141/4”
FIRESTOP RADIATION 
SHIELD
111/4” 121/4” 131/4” 141/4”
WALL THIMBLE 111/4” 121/4” 131/4” 141/4”
CAS CEILING 
SUPPORT
NA 121/4” NA 141/2”
CAS WALL THIMBLE NA 121/4” NA 141/4”
REDUCED 
CLEARANCE 
SUPPORT BOX
NA 101/4” NA NA
above that where the Support Box is located. 
Example: in a multistory home where the 
appliance is on the ground oor (Support 
Box is in the 1st oor ceiling), you would 
need a Firestop Radiation Shield at the 2nd 
oor ceiling, and at the 3rd oor ceiling, etc., 
including where the chimney penetrates into 
the attic.  Figure 7 shows a typical 2-story 
installation with an attic. 
Note: a Firestop Radiation Shield is not 
installed where the chimney penetrates 
through the roof. The Firestop Radiation 
Shield is installed on the underside of the 
ceiling/oor framing, with the cylindrical 
“tube” portion of the shield pointing 
upward. (Fig 8). Use a minimum of either 
(1) 8 penny nail or (1) #8, 1-1/2” wood screws 
per corner. Refer to Table 2 for framing 
requirements.
opening and maintain the 2-inch clearance to 
combustibles.
6. Install Firestop Radiation Shield:  A 
Firestop Radiation Shield is required in 
multistory installations at each oor penetration 










