User guide
15
WALL
PLUMBERS
STRAP/
TAPE
45°
ELBOW
45°
ELBOW
DIMENSION 
FROM TABLE 2
"H" OBTAINED 
adjoining rooines, steep pitched 
roofs, and other similar factors can 
result in poor draft, or down drafting. 
In these cases, increasing the vent 
height or switching to the High Wind 
Termination Cap may help to solve the 
problem. 
Step 9.  Slip the Storm Collar over 
the Pipe Section, and push it down to 
the top of the Roof Flashing (Fig. 18).  
Use non-hardening sealant between 
the Storm Collar and the Pipe Section.  
Step 10. Holding the bottom of the 
Termination Cap only, twist lock 
the cap onto the last Pipe Section 
protruding above the rooine.
 For multi-story vertical 
installations, a Ceiling Firestop is 
required at the second oor, and any 
subsequent oors (Fig. 19). Refer 
to Table 1, page 8. Cut and frame a 
square opening for installation of the 
Ceiling Firestop.
 If Vent passes through any 
occupied areas above the rst oor, 
including closets and storage spaces, 
it must be enclosed. The enclosure 
may be framed and sheetrocked with 
standard construction materials, but 
required clearances to combustibles 
must be maintained. Consult the 
appliance manufacturer’s installation 
instructions for the minimum allowable 
clearance between the outside of 
the vent pipe, and the combustible 
surfaces of the enclosure. Do not ll 
required air spaces with insulation.
 If venting system passes through 
an attic space the Attic Insulation 
Shield or a chase enclosure must be 
installed to prevent contact between 
Minim
Feet Meters
Flat to 7/12 1 0.3
Over 7/12 to 8/12 1.5 0.46
Over 8/12 to 9/12 2 0.61
Over 9/12 to 10/12 2.5 0.76
Over 10/12 to 11/12 3.25 0.99
Over 11/12 to 12/12 4 1.22
Over 12/12 to 14/12 5 1.52
Over 14/12 to 16/12 6 1.83
Over 16/12 to 18/12 7 2.13
Over 18/12 to 20/12 7.5 2.29
Over 10/12 to 21/12 8 2.44