Specifications

Electric Boosted Solar
7
H3163 025247 Rev. D
Installer’s Guide
ow and return pipes from the solar
collectors to the water storage tank
have a minimum of continuous fall
pipes have no high points that
allow air to be trapped
the minimum number of bends in
the pipes are used.
Flow and return lines should be
neatly installed and hidden inside the
roof cavity if possible.
Take care when running ow
and return lines through the roof,
cladding and the eaves.
Note: Where roof and
the eaves are made from
asbestos, specialised handling
and advice is necessary.
Minimum 5°
continuous fall
To collectors
Use minimum
number of bends
Must fully
insulate flow
and return
pipes
Minimum 5°
continuous fall
To collectors
Non continuous
fall
To collectors
Incorrect Correct
Ensure flow and return pipes from the solar collectors to the
water storage tank have a minimum of 5° continuous fall