Setting Up the Interlock Relay (Force On) Feature
Relays 1-4 can be set up as interlock relays. To set up the relays for the
interlock feature:
1. Access the SetupRelayAction menu and set the action to off.
2. In the Advanced features – User menu program any of the digital
inputs to Force On any of the internal relays (1-4).
3. Connect a switch or dry contact between the +5V terminal and the
corresponding digital input (dI-1 to dI-4) terminal.