bAUd Communications baud rate (992): Select 300, 1200, 2400, 4800,
9600, 19.2, 28.8, or 57.6. This number must match the baud rate
used by the host computer. The data format is 8 bits, 1 stop bit,
No parity.
nAt No Activity Timer (992): Select OFF to 99. If a number is set, the
control will expect access by the host computer. If no access is
detected within that time, the control will indicate an error, CHEC
LorE and go to the set point indicated by CFLt.
CFLt Communication Fault Mode (992): Select 1 or 2. 1 = On
Communication fault use local Set Point. 2 = On Communications
fault use CFSP.