Product Overview

DWYER INSTRUMENTS, INC. | dwyer-inst.com58
Differential Pressure Transmitters,
Air & Gas
PRESSURE
DIFFERENTIAL PRESSURE TRANSMITTERS ±0.25, ±1, OR ±2% ACCURACY
One-Touch
®
Digital Push-Button Calibration Technology
The Series 616KD Differential Pressure Transmitters ±0.25, ±1, or ±2% Accuracy
with One-Touch
®
digital push-button calibration technology are designed for
simplicity, making them the ideal choice for installers and maintenance professionals.
These instruments not only alleviate cumbersome turn pots typically found in most
transmitters, but eliminate entirely the need to span the instruments during calibration.
With a single digital push-button, both ZERO AND SPAN are calibrated properly,
nothing else is required. No additional reference pressure sources or separate
calibration devices are necessary.
FEATURES/BENEFITS
Simple calibration push-button sets back zero and span, saving time installing and
over the service life
Cost effective and compact device suitable for OEM applications where space,
simplicity, and value are key
Ranges and accuracy selection cover a wide range of applications minimizing
components and determining standardizing on design
• Optional1/8˝NPTprocessconnectionallowsforusewithmetalbarbedttingsor
compressionttingsforusewithmetaltubing
Optional plenum rated units meeting UL Standard 2043 are available
APPLICATIONS
Air handlers
Variable air volume
• Duct pressure
• Filter monitoring
5/16
[7.94]
OPTIONAL
TERMINAL
COVER
5/8
[15.88]
3-21/64
[84.53]
ø5/32
[3.97]
MOUNTING
HOLE
2 PLACES
7/8
[22.23]
1-1/32
[26.19]
2-13/32 [61.12]
2-1/4 [57.15]
1/2
[12.70]
2-13/32
[61.12]
1/2 [12.70]
1-1/2
[38.10]
SPECIFICATIONS
Service: Air and non-combustible, compatible gases.
Wetted Materials: Consult factory.
Accuracy: 616KD-A: ±0.25% FS; 616KD-B: ±1% FS, 616KD: ±2% FS.
Stability: ±1% FS/year.
Temperature Limits: 0 to 140°F (-17.8 to 60°C).
Compensated Temperature Range: 20 to 122°F (-6.67 to 50°C).
Pressure Limits: 2 psig (ranges 5 in w.c. or lower); 5 psig (ranges 10 to 40 in w.c.).
Thermal Effect: 616KD-A: ±0.02% FS/°F; 616KD-B: ±0.04% FS/°F; 616KD:
±0.06% FS/°F, includes zero and span.
Power Requirements: 4-20 mA output: 10-35 VDC (2-wire) or 12-26 VAC (4-wire);
5 V output: 10-35 VDC (3-wire) or 12-26 VAC (4-wire); 10 V output: 13-35 VDC (3-
wire) or 12-26 VAC (4-wire) for 616KD A and B. 16-36 VDC (2-wire or 3-wire): 20-28
VAC (3-wire) for 616KD.
Output Signal: 4-20mAoroptionwitheldselectable0-10,0-5,2-10,1-5V.
Zero and Span Adjustments: Push button.
Loop Resistance: 4-20mAoutput(DC):0to1250Ωmax.Rmax=50(VpsDC-10)
Ω;4-20mAoutput(AC):0to1200Ωmax.Rmax=50(1.4VpsAC-12)Ω;Voltage
output:5KΩminimum.
Current Consumption: 24mAmaxfor616KDAandB.21mAmaxfor616KD.
Electrical Connections: Screw-type terminal block.
Process Connections: Barbed,dualsizetot1/8˝and3/16˝(3mmand5mm)ID
rubber or vinyl tubing.
Enclosure Rating: NEMA 1 (IP20).
Mounting Orientation: Vertical with pressure connections pointing down.
Weight: 1.8 oz (51 g).
Agency Approvals: CE, optional plenum rated units meet UL standard 2043.
Optional
protective cap
Integral DIN rail
mounting kit
Digital push-button sets
both zero and span
SERIES 616KD
V
V
I
I
D
D
E
E
O
O
O
O
N
N
L
L
I
I
N
N
E
E
Optional NPT
connection block
YEAR LIMITED
WARRANTY
ACCESSORIES
Model Description
A-360
A-618
Aluminum DIN rail 1 m
Protective terminal cap
MODEL CHART
Example 616KD -A -12 -AT 616KD-A-12-AT
Series 616KD Differential pressure transmitter
Accuracy A
B
0.25% FS accuracy
1.0% FS accuracy
2.0% FS accuracy
Range 00
01
02
03
04
05
06
07
08
10
11
12
13
14
15
50
51
57
52
53
54
55
56
58
0 to 1 in w.c.
0 to 2 in w.c.
0 to 3 in w.c.
0 to 5 in w.c.
0 to 10 in w.c.
0 to 15 in w.c.
0 to 20 in w.c.
0 to 25 in w.c.
0 to 40 in w.c.
0 to 250 Pa
0 to 500 Pa
0 to 750 Pa
0 to 1250 Pa
0 to 2500 Pa
0 to 5000 Pa
0 to ±1 in w.c.
0 to ±2 in w.c.
0 to ±3 in w.c.
0 to ±5 in w.c.
0 to ±10 in w.c.
0 to ±250 Pa
0 to ±500 Pa
0 to ±750 Pa
0 to ±1250 Pa
Options AT
FC
NIST
TC
V
N
PR
Aluminum tag
Factory calibration
NISTcertication
Terminal cover
Voltageoutput0-5,1-5,0-10,2-10VDC(eld
selectable)
1/8˝femaleNPT
Plenum rated
Note: 0.25% FS accuracy is not available in the following ranges 00, 01, 10, 11, 50,
51, 54, 55

Summary of content (1 pages)