Manual
OPERATING PRINCIPLE
Capacitance and Dielectrics
Capacitance is the property of two or more conductors to store a charge
when  there  is  a  voltage  difference  between  the  conductors.  In  other
words capacitance relates the voltage between two conductors and the
amount of charge that can be held on the conductors (i.e., the number
of  electrons).  Capacitance  is  measured  in  Farads.  Since  a  Farad  of
capacitance represents a  very large charge storage capacity, most
capacitance encountered is generally measured in microFarads (µF, 10-
6) or picoFarads (pF, 10-12). Capacitances encountered in level sensing
applications are generally in the 10’s or 100’s of pico Farads range.
The material  between the conductors affects the  capacitance also.
Insulating materials do not allow free movement of electrons, however
in an electric field the molecules of these materials will tend to align with
the field thus storing energy. This is called the dielectric effect and these
materials are often referred to as dielectrics. When placed between two
conductors the energy  storage  capability of these  dielectrics  will allow
more  charge  to  be  stored  on  the  conductors  for  a  given  voltage
difference thus increasing the capacitance between the conductors. The
ratio of capacitance change caused by these dielectrics is referred to as
the  dielectric  constant.  Different  materials  have  differing  dielectric
constants and  will  consequently  change  the capacitance  between two
conductors more or less depending on the value of this constant. This
value ranges  from  1.0  for  a vacuum  to  over  100  for certain  materials.
The dielectric constant for air is very close to 1.0 and usually assumed
to be exactly 1.0.
Capacitive level sensors determine the level of material by changes in
probe capacitance  resulting from  the  movement  of  dielectric materials
between the probe and the reference ground electrode such as a tank
wall. Since measuring very small capacitance changes (less than 1 pF)
can be problematic in industrial environments, capacitance level sensing
tends to be most effective for materials with a dielectric constant greater
than  1.2.  Since  the  difference  in  capacitance  is  being  measured,  it  is
also  possible  to  detect  the  level  of  two  immiscible  liquids  that have
different dielectric constants such as oil and water.
Measurement
The CRF2 uses an impulse RF admittance measurement technique to
measure the probe capacitance. The impulse admittance measurement
offers  advantages  over  other  techniques in  that  it  produces  minimal
emissions  to  interfere with  other  communication  or  instrumentation
systems. The CRF2 continuously measures the probe capacitance.
Using this capacitance measurement, it computes a linear value with 0%
at  the  zero  calibration  value  and  100%  at  the  span  calibration  value.
From this  the output current  is computed  and generated. Since  no
assumptions are made regarding the relative value of the zero and span
calibration capacitances, the output can be set to measure from low to
high capacitance or high to low capacitance. 
INSTALLATION
Unpacking
Remove the CRF2 from the shipping carton and inspect for damage. If
damage is found, notify the carrier immediately. 
Materials
The  CRF2 may  be used  to detect  level of  a variety  of materials.
Conductive materials such as  water require an insulated  probe for
proper  operation.  When  used  with  a  conductive  material,  the  material
itself must be grounded to the reference ground of the CRF2. This may
be done through a conductive tank wall or using an optional reference
ground electrode.  Dry  non-conductive  materials  may  use  either  an
insulated or uninsulated probe. Capacitance level measurement is best
applied when  the  material  dielectric  constant is  greater than  1.2.  With
non-conductive materials, particularly low dielectric materials, the probe
should be spaced more closely to the reference ground to increase the
base capacitance and ensure reasonable sensitivity. The limiting factor
for spacing will be to ensure that material  buildup  around the probe is
avoided. For conductive materials this will be less of a concern since the
dielectric  insulator  around  the  probe  is  the  predominant  factor  in  the
capacitance changes with level. 
Example
Series
Enclosure
Probe Type
Ground
Process
Connection
Probe Length
Options
CRF2
CRF2
W
W
R
R
R
C
0
0
A
U
1T
1T
2T
3T
1B
2B
3B
1S
2S
3S
1F
2F
3F
4F
5F
6F
048
XXX
M20
M20
CRF2-WR01T-048-M20
Capacitive Level Transmitter
Weatherproof
Remote Mount Weatherproof Housing
Rod
Cable
None Included
Attached ground rod (3˝ or 4˝ flange process connection types only)
Unattached ground rod
3/4˝ NPT male
1˝ NPT male
1-1/2˝ NPT male
3/4˝ BSPT
1˝ BSPT
1-1/2˝ BSPT
1˝ sanitary clamp
1-1/2˝ sanitary clamp
2˝ sanitary clamp
2˝ 150# flange, 316 SS
2˝ 150# flange, PVC
3˝ 150# flange, 316 SS
3˝ 150# flange, PVC
4˝ 150# flange, 316 SS
4˝ 150# flange, PVC
Insertion length in inches. Example 048 is 48˝ length.
Rod Type: minimum: 24˝, maximum: 144˝
Cable Type: minimum: 24˝, maximum: 360˝
M20 conduit connection with cable gland




