Hi High Alarm Only. A1Hi appears in the Secondary Menu.
HiLo High and Low Alarms. Both A1Lo and A1Hi appear in the Secondary
Menu, and share the same Alarm 1 Relay output.
SF Seal Failure ONLY will trigger Alarm.
0t Over Temperature Failure ONLY will trigger Alarm
SF0t Both Seal Failure and Over Temperature Failure will trigger Alarm.
With the Alarm Function settings on
0FF, SF, 0t, SF0t certain alarm related menu items
will disappear as those menu items do not apply.
A1t Alarm 1 Type: Select AbS or dE. Factory default is AbS.
AbS Absolute Alarm that may be set anywhere within the values of SCAL and
SCAH and is independent of SP1H.
dE Deviation Alarm that may be set as an offset from SP1H. As SP1H is
changed the Alarm Point will track with
SP1H.
A1rE Alarm 1 Reset: Select 0n0F or HoLd. Factory default is 0n0F.
0n0F Automatic Reset.
HoLd Manual Reset. Reset (acknowledge) by simultaneously pressing the
INDEX & DOWN ARROW keys for 5 seconds.
A1Pi Alarm 1 Power Interrupt: Select 0n or 0FF. Factory default is 0FF.
0n Alarm Power Interrupt is 0n.
0FF Alarm Power Interrupt is 0FF.
A1iH Alarm 1 Inhibit: Select 0n or 0FF. Factory default is 0FF.
0n Alarm Inhibit is 0n. Alarm action is suspended until the process
value first enters a non-alarm condition.
0FF Alarm Inhibit is 0FF.
A1St Alarm 1 Output State: Select CL0S or 0PEn. Factory default is CL0S.
CL0S Closes Contacts at Alarm Set Point.
0PEn Opens Contacts at Alarm Set Point.
A1LP Alarm 1 Lamp: Select 0onor 0oFF. Factory default is 0on.
0on Alarm Lamp is ON when alarm contact is closed.
0oFF Alarm Lamp is OFF when alarm contact is closed.
A1td Alarm 1 Time Delay: Select 0FF or1 to 8000 seconds. Factory default is 0FF.
0FF Alarm function will operate when triggered at programmed Alarm
Set Point.
1-8000 Alarm function will only operate once the programmed time has
elapsed after the alarm was triggered by the Alarm Set Point.
21
AL2
With
will d
A2t
A2rE
A2Pi
A2iH
A2St
A2LP
A2td