User Manual

PROGRAMMING CHART
Use the charts on this and the next page to record the values in your application. You may
want to photocopy the pages if you plan to make programming changes.
Menu Item Default Set At Description
Primary
PV SP1H XXXX Home Position, Process Variable &
SP1H's Value displayed
Menu Item Default Set At Description
SP1H 23.1 Set Point 1 value (default is in feet)
SP1L 0.0 Set Point 1 off value (default is in feet)
SP2H 23.1 Set Point 2 value (default is in feet)
SP2L 0.0 Set Point 2 off value (default is in feet)
A1Hi 23.1 Alarm 1 (high) value (default is in feet)
A2Lo 2.0 Alarm 2 (low) value (default is in feet)
SFS1 120 Pump 1 Seal Failure Set Point
Secondary
SFS2 120 Pump 2 Seal Failure Set Point
P1rn XXXX Total ON Time for Pump 1 in HOURS
since last reset
P2rn XXXX Total ON Time for Pump 2 in HOURS
since last reset
P1SF ---- Pump 1 Reset for Seal Failure (---- or FAIL)
P2SF ---- Pump 2 Reset for Seal Failure (---- or FAIL)
P1OT ---- Pump 1 Reset for Over Temperature
(---- or FAIL)
P2OT ---- Pump 2 Reset for Over Temperature
(---- or FAIL)
Menu Item Default Set At Description
SECr 4 Security Selection
SCAH 23.1 Scale High value (default is in feet)
SCAL 0.0 Scale Low value (default is in feet)
dPt 0.0 Decimal Point Positioning
S1St POut Set Point 1 State (selectable POut
(Pumping Out) or PIn (Pumping In))
Secure
S2St POut
Set Point 2 State (selectable POut
(Pumping Out), PIn (Pumping In), or off)
LdLg On Lead/Lag (selectable on or off)
InPC 0.0 Input Correction
OSUP On
Zero Suppression (selectable on or off)
InP Curr Input (selectable current or voltage)
POT AUtO
Pump Over Temperature controller action
(selectable automatic or manual reset)
26