Owner's manual

Secure Menu
Press the UP ARROW and Enter keys for 5 Seconds to start the menu.
Press INDEX to advance to the next menu item. Press UP ARROW or
DOWN ARROW to change the value in the display. Press ENTER to retain
the value. OUTPUTS ARE DISABLED (TURNED OFF) WHILE CONTROL IS IN
THE SECURE MENU.
SECr Security Code: See the Security Level Selection and the Password Table
on page 10, in order to enter the correct password. Factory Default is 4.
InP Input Type: Select one of the following. Refer to the Input wiring section for
the proper wiring. Factory Default is Curr.
Curr DC Current Input 0.0 to 20.0 or 4.0 to 20.0 mA.
UOLt DC Voltage Input 0.0 to 10.0 or 2.0 to 10.0 volts.
- - - - Reserved
InPC Input Correction: Select ±500 counts. This feature allows the input value to
be changed to agree with an external reference or to compensate for
sensor error. Note: InPC is reset to zero when the input type is changed,
or when decimal position is changed.
LdLg Lead / Lag: Select On or O F F. Factory default is O n . (See page 11).
On The Lead/Lag function is enabled. The outputs of SP1 and S P 2
will alternate.
OFF The Lead/Lag function is disabled.
OSUP Zero Suppression: Select On or OFF. Factory default is O F F.
OFF The input range will start at 0 (zero) Input.
On The input range will start at 4.00 mA or 2.00 V.
dPT Decimal Point Positioning: Select 0, 0 . 0 , 0.0 0 , or 0 . 0 00. All Menu items
related to the input will be affected. Factory default is 0.0.
PEA The Peak feature stores the highest input the control has measured since
the last reset or Power On. At Power On PEA is reset to the present
input. To manually reset the value P E A must be in the lower display.
Press the ENTER key to reset. P EA will be reset and display the
present input value.
UAL The Valley feature stores the lowest input the Controller has measured
since the last reset or Power On. At Power On UAL is reset to the present
input. To manually reset the value U A L must be in the lower display.
Press the ENTER key. UAL will be reset and display the present
input value.
15