User guide
Multi Process Meter    Instruction Manual 
10 
Process Input 
INPUTS  Field selectable: 
0-20, 4-20 mA, 10 V (0-5, 1-5, 0-10 V), Modbus PV (Slave). 
ACCURACY  ±0.03% of calibrated span ±1 count, 
square root & programmable exponent accuracy . 
range: 10-100% of calibrated span. 
TEMPERATURE 
DRIFT 
0.005% of calibrated span/C max from 0 to 65C ambient, 
0.01% of calibrated span/C max from -40 to 0C ambient. 
SIGNAL INPUT 
CONDITIONING 
Linear, square root, programmable exponent, or 
round horizontal tank volume calculation. 
MULTI-POINT 
LINEARIZATION 
2 to 32 points for PV or PV1. 
2 to 8 points for PV2 (Dual-scale Level feature). 
PROGRAMMA-
BLE EXPONENT 
1.0001 to 2.9999. 
ROUND H TANK  Diameter & Length: 999.999 inch or cm calculates volume 
in gallons or liters respectively. 
LOW-FLOW 
CUTOFF 
0-999999 (0 disables cutoff function). 
DECIMAL POINT  Up to five decimal places or none: 
d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd. 
CALIBRATION 
RANGE 
Input 
Range 
Minimum Span 
Input 1 & Input 2 
4-20 mA  0.15 mA 
10 V  0.10 V 
An error message will appear if the input 1 and input 2 
signals are too close together. 
INPUT 
IMPEDANCE 
Voltage ranges: greater than 500 k 
Current ranges: 50 - 100  
(depending on resettable fuse impedance).
INPUT 
OVERLOAD 
Current input protected by resettable fuse, 30 VDC max. 
Fuse resets automatically after fault is removed. 
F4 DIGITAL INPUT 
CONTACTS 
3.3 VDC on contact. Connect normally open contacts 
across F4 to COM. 
F4 DIGITAL INPUT 
LOGIC LEVELS 
Logic High: 3 to 5 VDC. 
Logic Low: 0 to 1.25 VDC. 










