User guide
Multi Process Meter    Instruction Manual 
12 
Isolated 4-20 mA Transmitter Output 
OUTPUT 
SOURCE 
Process variable (PV), max, min, set points 1-8, Modbus 
input, or manual control mode. 
SCALING RANGE  1.000 to 23.000 mA for any display range. 
CALIBRATION  Factory calibrated: 4.000 to 20.000 = 4-20 mA output. 
ANALOG OUT 
PROGRAMMING 
23.000 mA maximum for all parameters: 
Overrange, underrange, max, min, and break. 
ACCURACY  ± 0.1% of span ± 0.004 mA. 
TEMPERATURE 
DRIFT 
0.4 µA/C max from 0 to 65C ambient, 
0.8 µA/C max from -40 to 0C ambient.
Note: Analog output drift is separate from input drift.
ISOLATED 
TRANSMITTER 
POWER SUPPLY 
Terminals I+ & R: 24 VDC  10%. May be used to power the 
4-20 mA output or other devices. Refer to Figure 5 on page 
17 and Figure 16 on page 23. 
All models rated @ 40 mA max. 
EXTERNAL LOOP 
POWER SUPPLY 
35 VDC maximum. 
OUTPUT LOOP 
RESISTANCE 
Power supply  Minimum  Maximum 
24 VDC  10  700  
  35 VDC (external)  100  1200  
Modbus
®
 RTU Serial Communications 
SLAVE ID  1 – 247 (Meter address). 
BAUD RATE  300 – 19,200 bps. 
TRANSMIT 
TIME DELAY 
Programmable between 0 and 199 ms. 
DATA  8 bit (1 start bit, 1 or 2 stop bits). 
PARITY  Even, Odd, or None with 1 or 2 stop bits. 
BYTE-TO-BYTE 
TIMEOUT 
0.01 – 2.54 second. 
TURN AROUND 
DELAY 
Less than 2 ms (fixed). 
Note: Refer to the Modbus Register Tables located at www.dwyer-inst.com for 
details. 