Transmitter Supply Voltage Selection (P+, P-) 
All meters, including models equipped with the 12/24 VDC power 
option, are shipped from the factory configured to provide 24 VDC 
power for the transmitter or sensor. 
If the transmitter requires 5 or 10 VDC excitation, the internal 
jumper J4 must be configured accordingly. 
To access the voltage selection jumper: 
1.  Remove all the wiring connectors. 
2.  Unscrew the back cover. 
3.  Slide out the back cover by about 1 inch. 
4.  Configure the J4 jumper, located behind the input signal 
connector, for the desired excitation voltage as shown. 
Figure 6. Transmitter Supply Voltage Selection
Connections 
All connections are made to removable screw terminal connectors 
located at the rear of the meter. 
Use copper wire with 60°C or 60/75°C insulation 
for all line voltage connections. Observe all safety 
regulations. Electrical wiring should be performed 
in accordance with all applicable national, state, 
and local codes to prevent damage to the meter 
and ensure personnel safety. 