Programming Set and Reset Points 
High alarm indication: program set point above reset point. 
Low alarm indication: program set point below reset point. 
The deadband is determined by the difference between set and reset 
points. Minimum deadband is one display count. If the set and reset 
points are programmed with the same value, the relay will reset one 
count below the set point. 
Note: Changes are not saved until the reset point has been accepted. 
Setting Fail-Safe Operation 
In fail-safe mode of operation, the relay coil is energized when the 
process variable is within safe limits and the relay coil is de-energized 
when the alarm condition exists. The fail-safe operation is set 
independently for each relay. Select on to enable or select off to 
disable fail-safe operation. 
Programming Time Delay 
The On and Off time delays may be programmed for each relay 
between 0 and 999.9 seconds. The relays will transfer only after the 
condition has been maintained for the corresponding time delay. 
The On time delay is associated with the set point. 
The Off time delay is associated with the reset point. 
Relay Action for Loss of 4-20 mA Input (Loop Break) 
The loop break feature is associated with the 4-20 mA input. Each relay 
may be programmed to go to one of the following conditions when the 
meter detects the loss of the input signal (i.e. < 0.005 mA): 
1. Turn On (Go to alarm condition) 
2. Turn Off (Go to non-alarm condition) 
3.  Ignore (Processed as a low signal condition) 
Note: This is not a true loop break condition; if the signal drops below 
0.005 mA, it is interpreted as a “loop break” condition. 