Application #2: Pump Alternation Using Relays 3 & 4 
1.  Relays 1 and 2 are set up for low and high alarm indication. 
2.  Relays 3 and 4 are set up for pump alternation. 
Set and Reset Point Programming 
Relay  Set Point Reset Point Function
1  495  750  Controls low alarm 
2  7500  6900  Controls high alarm 
3  7000  900  Controls backup pump 
4 6000  1000  Controls main pump 
The following graphics provide a visual representation of a typical pump 
alternation application with high and low alarm monitoring: 
1.  Relay #4 turns the main pump on at 6000 gallons and turns it off at 
1000 gallons. 
2.  With the Pump Alternation feature activated, the next time the level 
reaches 6000 gallons, relay #3 transfers and starts the backup 
pump. 