User guide
Multi Process Meter    Instruction Manual 
71 
Noise Filter (filter) 
The noise filter is available for unusually noisy signals that cause an 
unstable process variable display. The noise filter averages the input 
signal over a certain period. The filter level determines the length of time 
over which the signal is averaged. The filter level can be set between 2 
and 199. The higher the filter level, the longer the averaging time and so 
the longer it takes the display to settle to its final value. Setting the filter 
level to zero disables the filter function. 
Noise Filter Bypass (bypass) 
The noise filter bypass changes the behavior of the meter so that small 
variations in the signal are filtered out but large abrupt changes in the 
input signal are displayed immediately. The bypass value determines 
the minimum amount of signal change to be displayed immediately. All 
signal changes smaller than the bypass value are filtered or averaged 
by the meter. The noise filter bypass may be set between 0.1 and 
99.9% of full scale. 
Rounding Feature (round) 
The rounding feature is used to give the user a steadier display with 
fluctuating signals. Rounding is used in addition to the filter function. 
Rounding causes the display to round to the nearest value according 
the rounding selected. See examples below: 
Rounding 
Selection 
Actual 
Value 
Display 
Value 
Actual 
Value 
Display 
Value 
1 12.022 12.022 12.023  12.023 
5 12.022 12.020 12.023  12.025 
10 12.024 12.020 12.025  12.030 