User guide
Multi Process Meter    Instruction Manual 
8 
SPECIFICATIONS 
Except where noted all specifications apply to operation at +25°C. 
General 
DISPLAY  Upper display: 0.60" (15 mm) high, red LEDs 
Second display: 0.46" (12 mm) high, red LEDs 
6 digits each (-99999 to 999999), with lead zero blanking 
DISPLAY 
INTENSITY 
Eight user selectable intensity levels. 
DISPLAY 
UPDATE RATE 
5/second (200 ms). 
OVERRANGE 
Display flashes 
999999. 
UNDERRANGE 
Display flashes 
-99999. 
DISPLAY 
ASSIGNMENT 
The upper (Big) and lower (Little) displays may be assigned 
to PV1, PV2, PCT, d r-u, d gross, d nt-g, max/min, max & 
min, set points, units (lower display only), or Modbus input. 
PROGRAMMING 
METHODS 
Four front panel buttons, digital inputs, PC and Panel Meter Pro 
software, Modbus registers, or cloning using Copy function. 
NOISE FILTER  Programmable from 2 to 199 (0 will disable filter). 
FILTER BYPASS  Programmable from 0.1 to 99.9% of calibrated span. 
RECALIBRATION  All ranges are calibrated at the factory. Recalibration is 
recommended at least every 12 months. 
MAX/MIN 
DISPLAY 
Max/min readings reached by the process are stored until 
reset by the user or until power to the meter is turned off. 
PASSWORD 
Three programmable passwords restrict modification of 
programmed settings. 
Pass 1: Allows use of function keys and digital inputs. 
Pass 2: Allows use of function keys, digital inputs and editing set/reset points. 
Pass 3: Restricts all programming, function keys, and digital inputs. 
POWER 
OPTIONS 
85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max 
or jumper selectable 12/24 VDC  10%, 15 W max. 
ISOLATED 
TRANSMITTER 
POWER SUPPLY 
Terminals P+ & P-: 24 VDC  10%. 12/24 VDC powered models 
selectable for 24, 10, or 5 VDC supply (internal jumper J4). 
85-265 VAC models rated @ 200 mA max, 12/24 VDC powered 
models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC 
supply. 
NON-VOLATILE 
MEMORY 
All programmed settings are stored in non-volatile memory 
for a minimum of ten years if power is lost. 
FUSE  Required external fuse: UL Recognized, 5 A max, slow 
blow; up to 6 meters may share one 5 A fuse. 