METER OPERATION 
The meter is capable of accepting current (0-20 mA, 4-20 mA) and 
voltage signals (0-5 V, 1-5 V, 0-10 V,  10 V) and displaying these 
signals in engineering units from -99999 to 999999 (e.g. a 4-20 mA 
signal could be displayed as -50.000 to 50.000). 
The dual-line display can be customized by the user to operate in such 
a way as to satisfy a specific application. Typically the upper display is 
used for the process variable; while the second display is used for 
engineering units, custom legend, or set point indication. 
The analog input can be scaled to display the process in two different 
scales; for example: with d-SCAL enabled, the upper display could 
indicate level in feet and the second display could indicate the volume in 
gallons. 
Additionally the meter can be set up to display the analog input on the 
upper display and the Modbus input on the second display. The relays 
and analog output can be programmed to operate from the Modbus PV 
input. 
Front Panel Buttons Operation 
Button 
Symbol 
Description 
Press to enter or exit Programming Mode, 
view settings, or exit max/min readings 
Press to reset max/min readings or other 
parameter/function assigned through the User 
menu 
Press to display max/min readings or other 
parameter/function assigned through the User 
menu 
Press to acknowledge relays or other 
parameters/function assigned through the 
User menu 
Function Keys Operation 
During operation, the programmable function keys operate according to 
the way they have been programmed in the Advanced Features – User 
menu. 
The table above shows the factory default settings for F1, F2, and F3. 