User Manual
10
RTU Mode: 
To Read Instruction 
To Read Response 
Message 
To Write Instruction 
To Write Response 
Message 
Machine address
01H
01H
Machine 
address 
01H
01H
Machine 
address 
01H
01H
Machine 
address 
01H
01H
Instruction 03H
01H
Instruction 03H
01H
Instruction
06H
05H
Instruction 06H
05H
10H
08H
10H
08H
10H
08H
Starting address of 
reading data 
00H
10H
Response data 
length (byte) 
04H
02H
To write 
data 
address 
01H
10H
To write data 
address 
01H
10H
00H
00H
01H
17H
03H
FFH
03H
FFH
To read data length 
(word/bit) 
02H
09H
Data content 1
F4H
01H
To write 
data 
content 
20H
00H
To write data 
content 
20H
00H
CRC low byte 
C0H
BBH
03H
CRC low 
byte 
DDH
8FH
CRC low byte
DDH
8FH
CRC high byte 
CBH
A9H
Data content 2
20H
CRC high 
byte 
E2H
9FH
CRC high byte
E2H
9FH
      CRC low byte
BBH
77H
      CRC high byte
15H
88H
CRC (Cyclical Redundancy Check) program example: 
unsigned int reg_crc = 0xffff; i = 0;   
while (length--) 
{ 
 reg_crc ^= RTUData[i];   
 i ++;  
 for (j = 0; j < 8; j++) 
 {  
  if (reg_crc & 0x01) reg_crc = (reg_crc >> 1) ^ 0xA001;   
  else    reg_crc = reg_crc >> 1;   
 } 
} 
return (reg_crc); 
11
INSTALLATION 
SCD series can be extended up to 8 modules and installed by DIN rail mounting. 
1
2
SCD unit
Mounting Panel
DIN rail
1
2
3
12
HOW TO SET UP CURRENT INPUT 
For normal input 
For current input (4 ~ 20mA, 0 ~ 20mA) 
JUMPER
PIN HEADER
JP1
DEFAULT SETTING
JUMPER
PIN HEADER
JP1