SPECIFICATIONS
Power Supply:
SC1090: 85 to 265 Vdc/Vac 50 to 400 Hz.
SCL1090: 12 to 24 Vdc/Vac 50 to 400 Hz. ±20%
Isolation: 1500 V rms between outputs, input, and power.
Set Points: Adjustable 0 to 100% of span.
Deadband: Adjustable 0.25% to 100% of span.
Drift: ±0.02% / °C typical, ±0.05% / °C maximum.
Ambient Temperature Range:
Operating: 0° to 55° C (32° to 131° F)
Storage: -40° to +80°C (-40° to +176°F)
Humidity Conditions: 0 to 90% up to 40 °C non-condensing, 10 to 50%
at 55 °C non-condensing.
Input impedance:
Voltage input: 1 megohm.
Current input:10 ohms.
Relay output: SPDT, one per set point, 5A @ 250 VAC, resistive.
Latch circuit reset: Automatic at power up. Manual with reset
switch on front of module.
Indicators: One dual color LED per set point. Red = relay on,
green = relay off.
AL
DB
RESET
DIN EN 50022-35
(not supplied)
ADAPTER BRACKET
FOR SURFACE MOUNTING
(OPTIONAL)
KIT#: 1007-35DINADPTR
(1.40)
35.5
(0.886)
22.5
(2.950)
75
(3.880)
98.5
7
10
8
11
9
12
B
A
MODE
1234
LO
HI
DIR
ALARM A
REV
LATCHING
NON LATCHING
SW2
MODE
5678
LO
HI
DIR
ALARM B
REV
KEY
=ON
= OFF
BLANK =
NOT
APPLICABLE
SW1
290-2887
SW4
VOLTAGE
CURRENT
UNIPOLAR
BIPOLAR
ZERO BASED
ZERO +20%
MODE
1234
OUTPUT
DUAL
SINGLE
INPUT
10mV/1mA
50mV/5mA
100mV/10mA
200mV/20mA
0.5V/50mA
1V/100mA
5V
10V
12345678
RANGE
1 2 3 4 5 6 7 8
ON
ON
1 2 3 4
ON
ON
1 2 3 4 5 6 7 8
ON
ON
All dimensions in
millimeters (inches)
DIMENSIONS