ULSX‐CALCONFIGURATION(continued) StepSeven
Pump/Valve Mode:This featureallowsyou to selectthe mode for a
control or latching relay.Pump/Valve mode is not active for
Switch/AlarmsOnlyor4‐20mATransmitterOnly.
o Simplex–Allowsfortherelaytobeusedasanautomaticfillor
empty.This is the default and only configuration when 1‐
Pump/Valveisselected.
o SimplexusedtoEmptyTank(example)
o Lead/Lag–Allowsforthetworelaystohaveuniquestartlevels
and a common stop level.The first relay will be identified as
the lead relay and thesecond relay as the lag.Each time the
lead level is reached, the first relay will always start.The lag
relaywillonlystartwhenthelaglevelisreached.Allrelayswill
stopatthecommonofflevel.
o Lead/LagusedtoEmptyTank(example)
o Duplex‐Allows for the two relays to have two different start
levels,acommonstoplevelandwillalternatetherelayswhen
the first start level is reached.The two relays will alternate
eachtimetheleadlevelisreachedandtheremainingrelaywill
start when the lag level is reached.All relays will stop at the
commonofflevel.
o DuplexusedtoEmptyTank(example)
o Not Applicable – Appears when this function is not available
(such as when Switch/Alarms Only or 4‐20mA Transmitters
Onlyareselected).
Note:Rightclickonanymenuthatyoumayhavequestionsontoopenthehelpmenu.
Note:Toreset,presstheClearScreenbutton.