ULSXCALCONFIGURATION(continued) StepSeven
Pump/Valve Mode:This featureallowsyou to selectthe mode for a
control or latching relay.Pump/Valve mode is not active for
Switch/AlarmsOnlyor420mATransmitterOnly.
o SimplexAllowsfortherelaytobeusedasanautomaticfillor
empty.This is the default and only configuration when 1
Pump/Valveisselected.
o SimplexusedtoEmptyTank(example)
o Lead/LagAllowsforthetworelaystohaveuniquestartlevels
and a common stop level.The first relay will be identified as
the lead relay and thesecond relay as the lag.Each time the
lead level is reached, the first relay will always start.The lag
relaywillonlystartwhenthelaglevelisreached.Allrelayswill
stopatthecommonofflevel.
o Lead/LagusedtoEmptyTank(example)
o Duplex‐Allows for the two relays to have two different start
levels,acommonstoplevelandwillalternatetherelayswhen
the first start level is reached.The two relays will alternate
eachtimetheleadlevelisreachedandtheremainingrelaywill
start when the lag level is reached.All relays will stop at the
commonofflevel.
o DuplexusedtoEmptyTank(example)
o Not Applicable Appears when this function is not available
(such as when Switch/Alarms Only or 420mA Transmitters
Onlyareselected).