ULSXCALTANKLEVELS/WRITETOUNIT StepSeven
ULSXCAL‐TankLevels:ThissectionofULSXCALiswhereyouenterapplicationmeasurementvalues.This
appliestoallversionsoftheSeriesULS.YoumustentertheSensorHeightandFillHeightvalues.
For the Series ULSS, ULSM and ULSL, the Sensor Height and Fill Height values determine the
operationalrangeforthe420mAoutput.
SensorHeight: Distancefrom
thebottomofthetanktothe
bottomofthetransducer.
FillHeight:Distancefromthe
bottomofthetanktothe
maximumliquidheight.
ULSXCAL‐Relay Values:(Series ULSS, ULSM andULSL only):ThissectionofULSXCALiswhereyouenter
theoperationalvaluesforrelays.Youmustentervalueswithinallofthefieldsshown.Thevaluefieldsshown
are based upon the configuration of the Series ULS.All values must be in the units of operation selected
aboveandarebaseduponunitsofliquid.AllrelayvaluesmustbegreaterthanLiquidEmpty(0)andlessthan
LiquidFull(FillHeight).
Example: Thissampleshows4
High Level Alarms.As the
level increases from the
bottom –up, each alarm will
activateat4”increments.
Example:Thissampleshowsa
2Pump
Lead/Lag operation
with a High and Low alarm.
The pumps will automatically
empty the tank and the
alarmswillactivateifthelevel
getstoohighorlow.
