User Manual
28of30 MN890570 RevA
TROUBLESHOOTING StepTwelve
FactoryDefault:Pressingthe“FactoryConfig”buttonintheConfigurationmenuwillreturnthescreentothe
following settings.Out of the box, the Series ULS will output a 4‐20 mA output that is maximized for its
operationalrange.
  SeriesULSS–4mA@4.1’(1.25m)awayand20mA@2”(5cm)awayfromsensor.
  SeriesULSM–4mA@8.2’(2.5m)awayand20mA@4”(10cm)awayfromsensor.
  SeriesULSL–4mA@18.0’(5.5m)awayand20mA@8”(20cm)awayfromsensor.
FactoryDefaultsTable
TestingtheTransmitter
1.  Connectamultimeterinserieswiththeblackwiretoreadthecurrentoutput.
2.  Verify that the current increases (tank filling) and decreases (tank emptying) appropriately in the
calibratedspan.
3.  Ifnot,carefullyobserveandattempttocorrelate
anyinstallation,levelorapplicationeventformore
specifictroubleshootingdirection.