ULSX‐CALCONFIGURATION StepSeven
ThissectionofULSX‐CALiswhereyouselecttheapplication’sconfigurationsettings.Startfromthetopand
worktothebottom,choosingtheselectionsthatareapplicabletoyourconfiguration.“ Not Applicable”will
automaticallyshowwhenaselectiondoesn’tapplytoyourconfigurationsettings,andyoumaymoveon.All
configurationsettings mustbeselectedorhave “Not Applicable”before youcan continueto the nextstep.
Note:PressingtheClearScreenbuttonwillresettheconfigurationtableandallowaccesstoallofthefeatures.
NumberofPumps:Thisfeatureallowsyoutoselectthenumber
of
pumpsorvalvesusedwithSeriesULS.Thisisthesettingthatactivates
thecontrolcapabilitiesofuptotworelays.Controlrelaysareoften
referredtoaslatchingrelays.
o Switch/Alarms Only – The relays will be standard single point
relays(Highand/orLowalarms).Relaysarenon‐latching.
o 1‐ Pump/Valve – One relay will be configured as a control or
latchingrelay (relaywillhave a start level anda separate stop
level).Use this setting to control one pump or valve for
automaticfillingoremptyingofatank.
o 2‐Pumps/Valves – Two relays are
configured as control or
latchingrelays.Eachrelaywill havea unique startlevel anda
common stop level.Use this setting to control two pumps or
valvesforautomaticfillingoremptyingofatank.
o 4‐20mATransmitterOnly–Thissettingwilldisengageallofthe
relays.Use this function if you are not using any relays and
usingonlythe4‐20mAcurrentoutput.
Note:Rightclickonanymenuthatyoumayhavequestionsontoopenthehelpmenu.
Note:Toreset,presstheClearScreenbutton.