6. All electrical power must be disconnected at the main service box, which
must be locked before connecting, inspecting, cleaning or servicing the
heater. This is an important precaution to prevent serious electric shock.
7. This is heater is not suitable for use in hazardous locations containing
explosive liquids or vapours. This heater has hot or arcing or sparking pads
inside. Do not use it in areas where gasoline, paint or ammable liquids are
used or stored.
8. This heater is not suitable for use in corrosive atmospheres such as marine
greenhouses or chemical storage areas.
9. This heater must be mounted at least 8 feet off the oor. For specic
clearances, please see next page.
Install heater away from trafc areas, maintaining clearances stated in gure
2 (below). The air ow direction should not be restricted (ie. by columns or
machinery). The air ow should wipe exposed walls rather than blowing directly
on them. When more than one heater is used in an area, heaters should be
installed so that the air discharge of each heater supports the air ow of the
others, to provide best warm air circulation as shown in gure 3.
GENERAL SAFETY INFORMATION
LOCATING HEATER
Improper installation or failure to follow the procedures outlined in this
instruction manual can result in serious electrical shock.
WARNING
Figure 2