User manual
Operating & Installation Manual for the GSC300 Engine Controller
13
CONTROLLER OVERVIEW
The GSC300 Features the Following Functions:
1. Controller Programming Adjustability
2. General Fault Conditions
3. Not In Auto
4. Low Battery Voltage Alarm
5. Oil Pressure Input
6. Coolant Temperature Input
7. Fuel Level/Auxiliary Input
8. Speed Signal Sensing
9. Adjustable Input Programming
10. Magnetic Pick-Up Capability Option
1: CONTROLLER PROGRAMMING ADJUSTABILITY:
Adjustable Parameter Ranges:
Crank Disconnect: 12 to 140Hz (Generator Output Version)
44 to 300Hz (Magnetic Pick-up Version)
Overspeed: 60 - 4156Hz (Generator Output Version) -OR DISABLED BY PC INTERFACE
300 - 8492Hz (Magnetic Pick-up Version) -OR DISABLED BY PC INTERFACE
Crank Tries: 1 to 10
Crank/Rest: 3 to 32 seconds
NOTE: If the engine speed seen by the controller does not go to zero during Crank Rest, the controller will
wait until the speed goes to zero before re-initiating the cranking sequence.
2: GENERAL FAULT CONDITIONS: The following scenarios can cause the unit to enter the
general fault condition:
Low Fuel/Auxiliary Failure (“XTR_FAIL”)
Low Oil
High Coolant Temperature
Overcrank
Overspeed
Loss of Speed (“SPDLOSS”)
The General Fault output is rated 300mA Max.