4
Timer adjustments
Glow Plug/Preheat: 0 - 255 seconds
Energize To Stop (ETS): Energizes for 15 seconds on failures, or energizes until 5 seconds after
engine speed goes to zero upon removing power from Start/Stop terminal
or removing the unit from manual mode using the front panel buttons.
Inputs
Speed Sensing:
-Optional Generator Output Speed Sensing or Magnetic Pick-Up Model
(Specified by customer at time of order)
Maximum Input Voltage: 300Vrms
Minimum Input Voltage: 0.7Vrms(Generator Output Sensing),
0.1Vrms(Magnetic Pick-Up version)
-60Hz Rejection Filter Included
-Loss of Speed Signal Included
Sender/Failure Inputs:
-Oil Pressure, Coolant Temperature, Fuel Level/Auxiliary Input
-Accepts standard industry low impedance (0-500 ohm) sender inputs
(VDO, Stewart-Warner, Datcom, Murphy, etc.)
-Data entry available for custom sender inputs
-Can be configured to accept a switched gauge failure through the PC interface
-Failure points adjustable