User manual

Operating & Installation Manual for the GSC300 Engine Controller
7
WIRING INSTALLATION GUIDELINES
Danger: Never work on the engine while its power is on. This controller does
not generate a warning signal prior to automatic engine start. Warning signs should
be placed on engine equipment indicating this important safety measure.
INSTRUCTIONS
Following these instructions will help avoid common installation problems during wiring and setup.
Battery must be disconnected before any wiring connections are made.
Wire length from the engine to the controller should not exceed 6 meters (20 feet).
Wiring size and type should be as specified below. Use stranded wire, since solid wire has a tendency to crack,
break and loosen over time.
TYPES AND SIZES
Terminal Wire Size
(AWG)
Current max. Function
1 12 40A Fuel Output Terminal
2 12 40A Auto(Battery +) Terminal Connection
3 12 40A Auto(Battery +) Terminal Connection
4 12 40A Crank Output Terminal
5 12 40A Ground Terminal Connection
6 12 40A Ground Terminal Connection
7 12 40A Preheat/ETS Terminal
8 12 40A Preheat/ETS Terminal
9 18 100mA Speed Signal Connection
10 18 100mA Speed Signal Connection
11 18 300mA Overcrank Output
12 18 300mA Overspeed Output
13 18 300mA High Temp Output
14 18 300mA Low Oil Output
15 18 300mA Low Battery Output
16 18 300mA Engine Run Output
17 18 100mA Not in Auto Output
18 18 300mA General Failure Output
19 18 7mA Start/Stop Input
20 18 7mA Oil Pressure Sender/Switch Input
21 18 7mA Temperature Sender/Switch Input
22 18 7mA Fuel Level/Auxiliary Sender/Switch
Input