User manual

26 of 30
4. Configurable Features of the GSC300
Features
Description
Crank
Disconnect
This is the frequency at which the GSC300 will disengage the crank,
keeping the fuel on to run the generator.
Speed
Source
Either generator output (gen o/p) or magnetic pickup (Mag). For
generator output you must buy the L-Version. For Mag pickup you
must buy the H version. The PC interface only hides/shows the
frequency display on the LCD. You can still use mag pickup if you have
this setting set to generator output but the LCD will display an invalid
frequency.
If set to magnetic pickup the maximum frequency that can be sensed is
3000Hz (100 teeth at 60Hz).
Over-Speed This is the frequency when the GSC300 will shutdown the generator
and indicate a failure.
High Temp
Setpoint
This is the value when the GSC300 will shutdown the generator and
indicate a high temperature failure.
Low Oil
Setpoint
This is the value when the GSC300 will shutdown the generator and
indicate a low oil pressure failure.
Delay to Start This is a time in seconds that the GSC300 will wait before starting the
generator.
Preheat Time This is the time in seconds that the GSC300 will turn on the Extra relay,
in order to preheat the generator. It is required that this option be
enabled in order to be used. If this option is chosen, Warm-up or
Energize to Stop (ETS) will not be available.
Battery
Voltage
This is the value in Volts that the GSC300 will alarm a low battery level.
This will not shut the generator down and will not generate a failure.
Crank Tries This value is the number of attempts the GSC300 will crank over the
generator.
Crank Time This is the time in seconds the GSC300 will continue to crank over the
generator.
Oil Bypass
Time
This is the time in seconds the GSC300 will wait before checking to see
if the Oil Pressure has reached a desirable level.
Cool-Down
Time
This is the time in seconds the GSC300 will wait before shutting the
generator down in order to allow sufficient cool down.
Warm-Up
Time
This is the time in seconds the generator will keep the Extra relay off in
order to allow the generator sufficient time to warm up. The extra relay
would be used to turn on a load in this case. This option must be enable
in order to be used. If this option is chosen, Preheat and ETS will not be
available. Please note that this function will be activated after the Oil
Bypass Time has expired.
Rest Time This is the time in seconds the GSC300 will wait before attempting to
turn the crank on for another crank attempt.