User manual

30 of 30
Constant Low oil
failures.
Low oil level
Choosing the sender setting
value to high, causing the
GSC300 to always fail since
the value of the sender is
always below the chosen
failure set point.
Oil delay time needs to be
extended to eliminate false
failures.
Faulty Sender
Add oil
Choose a lower sender
failure set point.
Increase the delay time
from 0.5 to 6 seconds.
Change out sender
Constant Temperature
failures.
Low coolant level
Choosing the sender setting
value to low, causing the
GSC300 to always fail since
the value of the sender is
always above the chosen
failure set point.
Faulty Sender
Add coolant
Choose a higher sender
failure set point.
Change out sender