7.4 Parameter List and Ranges 
If you already have a configuration file you can open and view it using the SWT-1000 Windows 
Software menu  
File Æ Open 
You can also connect the SWT-1000 to a PC (see section 7.2) and read back the parameters, 
SWT-1000 Æ Read parameters 
Once loaded into the software the parameter set may be printed via File Æ Print 
Normal Windows file handling rules apply. 
7.5 Parameters 
Parameters are changed in the sub menus from the drop down menu “Configuration“. Parameter 
list and ranges. Factory settings are shown in bold. 
Configuration < System >   
Machine factor  1.0000E-07 ... 1.0000 ... 9.9999E+07 
Minimum Measuring time  2 / 5 / 10 / 20 / 50/ 100 / 200 / 500 ms / 1/ 2 / 5 Seconds 
Min displayed measured value  1.0000E-12 ... 1 ... 1.0000E+12 
Alarm definition  Only System error System error OR Sensor Monitoring 
Configuration < Sensor >   
Sensor Type  Active / Passive 
Sensor input  Analog (Sign) / Digital (IQ) 
Sensor current minimum  0.5 ... 1.5 ... 25.0mA 
Sensor current maximum  0.5 ... 25.0mA 
Configuration < Analog output >   
Measuring range start value  0.0000 ... 90% of the end value 
Measuring range end value  1 … 2000.0 … 500000 
Output range  0 ... 20mA / 4 ... 20mA 
Time constant (Damping)  0.0 ... 9.9s 
Configuration < Limits >   
Status Limit 1 On / Off 
Status Limit 2 On / Off 
Mode Limit 1 Normal / Inverse 
Mode Limit 2 Normal / Inverse 
Lower Set point  Limit 1  0.1 … 200.00 … 500000 
Upper Set point  Limit 1  0.1 … 300.00 … 500000 
Lower Set point  Limit 2  0.1 … 400.00 … 500000 
Upper Set point  Limit 2  0.1 … 500.00 … 500000 
Configuration < Relay control >   
Switching of control A/B   
Selection of actuator  None (always control A) / Binary Input B1 
Delay time  0 ... 2.000 s 
Relay Assignment   
Control  A  Alarm / Sensor monitor / Limit 1 / Limit 2 / Window / On / 
Off 
Acknowledge  A  Without acknowledge (no hold function) / 
Relay held when control active / 
Relay held when control inactive 
Acknowledge  B  Alarm / Sensor monitor / Limit 1 / Limit 2 / Window / On / 
Off 
Acknowledge  B  Without acknowledge (no hold function) / 
Relay held when control active / 
Relay held when control inactive 