Alfa Electrical Ltd TAM House Ballymount Trading Estate Ballymount Road Lower Dublin 12 Telephone: 01-4600732 Fax: 01-4600732 ST MICHAELS HOUSE UNIT 94A LAGAN ROAD ELECTRICAL OPERATIONS AND MAINTENANCE MANUAL
St Michaels House Lagan Rd Job Ref: 2009-001 Electrical O&M Manual CONTENTS SECTION 1 GENERAL DESCRIPTION SECTION 2 ELECTRICAL CENTRES AND MAINS DISTRIBUTION SECTION 3 GENERAL SERVICES SECTION 4 LIGHTING AND EMERGENCY LIGHTING SECTION 5 COMMUNICATION SERVICES SECTION 6 FIRE ALARM SERVICES SECTION 7 SECURITY SERVICES SECTION 8 MECHANICAL SERVICES SECTION 9 TEST RESULTS & COMPLETION CERTIFICATES SECTION 10 OPERATING & MAINTENANCE PROCEDURES SECTION 11 AS-INSTALLED DRAWINGS Alfa Elect
St Michaels House Lagan Rd Job Ref: 2009-001 Electrical O&M Manual PROJECT TEAM Client: St Michaels House, Technical Services Dept, 89D Lagan Road, Dublin Industrial Estate, Glasnevin, Dublin 11. Contact: Paul Kenny Tel: 01-8303161 Architects: James Smyth Architects, Booterstown Ave 10-12, Blackrock, Co Dublin Contact: Vincent Traynor Tel: 01-2882661 M&E Consultants: Clarke and Associates, Academy Street, Kildare Town, Co Kildare.
St Michaels House Lagan Rd Job Ref: 2009-001 Electrical O&M Manual SECTION 1 - GENERAL DESCRIPTION The project involves the refurbishment of the existing building at Unit 94A, Lagan Road, Glasnevin, Dublin 11 into a new training centre for St Michaels House.
St Michaels House Lagan Rd Job Ref: 2009-001 Electrical O&M Manual SECTION 2 – ELECTRICAL CENTRES & MAINS DISTRIBUTION Supplier Details: Reg Farrell Engineering Unit 19 Oak Road Business Park, Western Industrial Estate, Dublin 12. Tel: (01) 4659010 Fax: (01) 4659011 Contact: Ciara John Keogh Electrical Unit 7, E.P.Mooney Buisness Centre, Longmile Road, Dublin 12.
St Michaels House Lagan Road Job Ref: 2009-001 Circuit Chart Sub Distribution Board SDB - 2 Terminal 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 Terminal 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 Cct Ref P01 P02 P03 P04 P05 P06 P07 P09 P08 Type Sockets Sockets Sockets Sockets Sockets Sockets Sockets Sockets Sockets Sockets Sockets Sockets Sockets P16 P16 P16 P19 P20 P22 P22 P22 Location Reception Reception Dining and Relaxation Kitchen and C
Box depth 300 STRUCTURE 1,5 mm steel sheet painted with RAL 7032 / 7035 textured finish. FLAT MOUNTING PLATE 2 mm galvanized steel sheet. DOOR reversible, with two square handles up to 1200 mm height, and one handle closing for 1400 mm height, painted RAL 7032 / 7035 textured finish with sealing gasket in continuous pour. GLAND PLATE Duly dimensioned, is fixed at the bottom of the box. THE SUPPLY INCLUDES structure, mounting plate, door, gland plate, all screws necessary for the assembly.
Miniature Circuit Breakers G60 Circuit Protection IEC 60898 IEC 60947-2 10kA Applications Performances Thermal setting In A Approval / Marking (A) 2-63 Rated voltage AC Un (V) 240/415 Minimum operating voltage UB min (V) 12 Tripping characteristics B-C-D Selectivity class 3 Mechanical/electrical endurance 20000/10000 Tropicalisation acc.
St Michaels House Lagan Rd Job Ref: 2009-001 Electrical O&M Manual SECTION 3 – GENERAL SERVICES Supplier Details: John Keogh Electrical Unit 7, E.P.Mooney Buisness Centre, Longmile Road, Dublin 12.
St Michaels House - Lagan Road Job Ref: 2009-001 General Services Schedule General Services Schedule of Equipment Item Manufacture Part No Supplier Switched Socket Outlets Fan Isolator Switch 20A Double Pole Switch c/w neon indicator Unswitched Spur c/w neon indicator Cooker Outlet 20A Double Pole Switch c/w neon indicator Phone Plate 1 Mod Grid Frontplate 1G Grid Frame Inter/Grid Switch 3 Gang Switch 1 Gang 2W Switch 4 Mod Grid Frontplate 4G Grid Frame 2W Grid 32 amp MCO Switch Dishwasher 32 amp MCO
Albany Plus TECHNICAL HOTLINE +44 (0)1268 563720 117 DECORATIVE 13 AMP SOCKET AVAILABLE DOUBLE POLE SWITCHING WITH NEON INDICATORS MATCHING SCREWS STYLISH CURVED DESIGN WITH WHITE INSERTS Blends unobtrusively into the environment UNIQUE 3-PIN “CHILD RESISTANT SHUTTER SYSTEM” Designed to inhibit access to the PRE-TREATED HEAT-CURED electricity supply, unless all 3 pins POWDER LACQUER FINISH of a standard British 13 Amp plug Ensures that the range is are in position durable and tarnish resistan
Logic Plus TECHNICAL HOTLINE +44 (0)1268 563720 19 WHITE CONTOURED TO DOUBLE POLE SWITCHING BLEND INTO THE Switches both live and neutral (neutral makes first, breaks WALL last) means added safety for the user OPTIONAL NEON INDICATOR SHOWS WHEN SWITCH IS ON 3mm SWITCH CONTACT GAP TASTEFUL WHITE, HIGH GLOSS, HIGH QUALITY THERMOSET MATERIAL Maintains appearance and resists scratching UNIQUE 3-PIN “CHILD RESISTANT SHUTTER SYSTEM” Designed to inhibit access to the TERMINAL MARKINGS electricity suppl
St Michaels House Lagan Rd Job Ref: 2009-001 Electrical O&M Manual SECTION 4 – LIGHTING AND EMERGENCY LIGHTING Supplier Details: Thorlux Lighting, 1st Floor, Unit H3, Centrepoint Business Park, Oak Road, Dublin 12. Tel: (01) 4604608 Fax: (01) 4604609 Contact: Paul Ford Total Lighting, Unit 7, E.P.Mooney Buisness Centre, Longmile Road, Dublin 12. Tel: (01) 4509999 Fax: (01) 4509544 Contact: Garrett Dwyer Emerald Electrical Wholesale, 198a Whitehall Road, Terenure, Dublin 12.
St Michaels House - Lagan Road Job Ref: 2009-001 Lighting Schedule Lighting Schedule Ref Item Manufacture Part No Supplier A Recessed Radiance 4*18w Body Recessed Radiance 4*18w Louvre Lamp: 18w Triphosphor, 400k Thorolux Thorolux Philips ALT 10276JF LVR10240 LMP9182 Thorolux Thorolux Philips B DOT Opal 38w, HF Lamp: 38w 2D Colour 84 Thorolux Philips 2DOT9903JF 38w22DCol84o Thorolux Total Lighting B1 DOT Opal 38w, HF with Emergency Inverter Pack Lamp: 38w 2D Colour 84 Thorolux Philips 2D
Recessed Radiance TYPE A Recessed T8 luminaires for general use and VDT areas G Steel body finished white G Satin anodised aluminium louvres G LG7:2005 (<1500 cd/m2 @ 65o) and faceted crossblade louvre versions available G High uniformity lighting with radial light distribution G Fits most ceiling types, may be lay-in or pulled-up G Supplied with side arm support kit G Daylite version, see page 27 LG7:2005 Range NOMINAL SIZE (mm) LAMP LG7:2005 VERSION. FACETED VERSION APPROX.
TYPE D Thoroproof Anti-corrosive polycarbonate luminaires for T8 and T5 lamps G High-impact and corrosion-resistant light grey, injection moulded polycarbonate body G Clear prismatic polycarbonate cover G Body and cover flame-retardant G Smooth easy-clean lines G Snug-fit polycarbonate cover clips (stainless steel option see page 42) G Fast installation via external stainless-steel brackets preserves IP rating G Optional narrow distribution reflector for rack lighting applications G Compli
St Michaels House Lagan Rd Job Ref: 2009-001 Electrical O&M Manual SECTION 5 – COMMUNICATIONS SERVICES Supplier Details: Beacon Communications, Unit A1, Nangor Road Business Park, Nangor Road, Dublin 12. Tel: (01) 4198485 / 4198488 Fax: (01) 4198606 Contact: Adrian Dunbar Total Lighting, Unit 7, E.P.Mooney Buisness Centre, Longmile Road, Dublin 12.
C5E-SPEC-01 Rev 1.0 CAT 5e 24 PORT PATCH PANEL Specifications Qualified Cat.5e Permanent Link/Channel of EIA T568A and T568B (ISO/IEC11801) 24port 19” 1U Height Gold plating: gold over nickel Silver plating: 1.25um, 5um Modularity Mechanical Performance Insertion Life: 750 cycles minimum IDC Life: 200 times (22-26 AWG Solid wire) minimum Plug/Jack Contact Force: 100g minimum using FCC-approved plug.
C5E-SPEC-03 CAT 5e EURO MODULE Specifications Size: 25×50×23mm Color: White Criteria: TIA/EIA T568-A Krone IDC CAT5e Mechanical Performance Material: Shell: ABS(UL94V-0) Jack: PBT Gold pin: Sn6.5-0.1(Y) Thickness of gold coated: 15um, 30um, 50um Contactor: Sn6.5-0.1(Y) Thickness of silver coated: 0.5um IDC: Copper conductor 0.4~0.64mm max.
St Michaels House Lagan Rd Job Ref: 2009-001 Electrical O&M Manual SECTION 6 – FIRE ALARM SERVICES Supplier Details: Siemens Limited Fitzwilliam Court Leeson Close Dublin 2 Tel: (01) 2162000 Contact: Derek Regan Greenhills Rainbow Ltd, 23A Greenhills Industrial Estate, Walkinstown, Dublin 12.
St Michaels House Lagan Rd Job Ref: 2009-001 Electrical O&M Manual Fire Alarm Schedule Ref Item 2-Loop Analogue Addressable Panel Mx-4200 12-Volt 7.
XP95 OPTICAL SMOKE DETECTOR incoming and outgoing supply via terminals L1 and L2 in the mounting base. A remote LED indicator requiring not more than 4mA at 5V may be connected between the +R and -R terminals. An earth connection terminal is also provided. XP95 Optical Smoke Detector s Part Number 55000-600/620/660 Operating Principles The XP95 optical detector uses the same outer case as the ionisation smoke detector and is distinguished by the indicator LED which is clear in standby and red in alarm.
XP95 MANUAL CALL POINT XP95 Manual Call Point (MCP) OPERATING PRINCIPLES The new Apollo XP95 EN54-11:2001 compliant Manual Call Point (MCP) is based on the KAC conventional MCP range. It is electronically and mechanically backward compatible with previous Apollo call points based on KAC’s World Series product. The address of each call point is set at the commissioning stage by means of a seven-segment DIL switch. Fig.16 A single bi-coloured alarm LED is provided on the call point.
Mx-4200 Fire Panel Analogue Addressable Fire Control Panel Insert zoom image HighRes Advanced Fire Panel Technology Product Data Sheet The Mx-4200 series is fully expandable from 1 to 2 loops complete with 2 on-board sounder circuits. The control panel consists of a simple to use LCD menu driven graphical interface, dual, flashbased microprocessor technology driven by a 4 Amp power supply and charger approved to EN54 parts 2 & 4.
Product Data Sheet User Manual User Manual MX-4100, MX-4200, MX-4400, Mx-4400/LE & Mx-4800 Fire Alarm Control Panels The operation and functions described in the manual are available from Software Versions Mx4100-019, Mx4200-019 and Mx4400-019 onwards.
St Michaels House Lagan Rd Job Ref: 2009-001 Electrical O&M Manual SECTION 7 – SECURITY SERVICES Supplier Details: Greenhills Rainbow Ltd, 23A Greenhills Industrial Estate, Walkinstown, Dublin 12. Tel: (01) 4602014 Fax: (01) 4503155 Contact: Paul Tracey Scott and O`Shea, Units G4 & G5 Calmount Calmount Park, Ballymount, Dublin 12.
St Michaels House Lagan Rd Job Ref: 2009-001 Electrical O&M Manual SECTION 8 – MECHANICAL SERVICES Mechanical Contractor: JRE Group, Western Road, Clonmel, Co Tipperary Tel: 052 87400 Fax: 052 87435 Contact: John Kinsella MCC Supplier Details: McCool Controls & Engineering Ltd U12 Docklands Innovation Centre East Wall Road Dublin 3 Tel: (01) 8550532 Fax: (01) 8550546 Contact: John Kinsella Contents: Boiler House Wiring Schedule MCC Workshop Drawings & Notes Gas Detection System Alfa Electric
St Michaels House Lagan Rd Job Ref: 2009-001 Electrical O&M Manual Boiler House Wiring Schedule Equipment Ref Switch Indication / Location Boiler BO/1 Test-Off-Auto Power on/fault Burner BU/1 Test-Off-Auto Boiler house Primary Pump Calorifier Constant temperature circuit P1 Test-Off-Auto Heating Pump Zone A P2 Test-Off-Auto Heating Pump Zone B P3 Test-Off-Auto Shunt Pump P7 Test-Off-Auto Hot Water Secondary Return Pump P9 Test-Off-Auto Running/Tripped Boilerhouse Running/Trippe
St Michaels House Lagan Rd Job Ref: 2009-001 Electrical O&M Manual SECTION 9 – TEST RESULTS & COMPLETION CERTIFICATES Contents: RECI Completion Cert Communication Services Test Results & Completion Cert Fire Alarm Completion Certificate Emergency Lighting Completion Certificate Alfa Electrical Ltd 29/01/2009
Cable ID: SMH LAGAN RD-DROP 01 Date / Time: 02/20/2009 08:25:55am Headroom: 8.4 dB (NEXT 36-45) Test Limit: TIA Cat 5e Perm. Link Cable Type: Cat 5e UTP Test Summary: PASS Operator: Your Name Software Version: 2.1200 Limits Version: 1.2800 NVP: 69.0% Model: DTX-1800 Main S/N: 9748109 Remote S/N: 9748110 Main Adapter: DTX-PLA002 Remote Adapter: DTX-PLA002 Wire Map (T568B) PASS 83 ft 1 2 1 2 3 6 3 6 4 5 4 5 7 8 7 8 S S PASS Worst Pair NEXT (dB) Freq.
St Michaels House Lagan Rd Job Ref: 2009-001 Electrical O&M Manual SECTION 10 – OPERATING & MAINTENANCE PROCEDURES Contents: Operating & Maintenance Procedures Safety Alfa Electrical Ltd 29/01/2009
OPERATING & MAINTENANCE PROCEDURES General Recommendations 1.1 Introduction Preventative Maintenance can be described as the routine inspection, testing and cleaning, adjustments and early detection of incipient trouble likely to cause breakdown. The efficient manner in which this is done can be assessed by freedom from breakdown and behavior of plant under abnormal and fault conditions.
SAFETY 1.1 General Statutory Regulations All parties involved in the operation and maintenance of the electrical installation must be aware and act under the requirements of the Health and Safety at Work Act 2005, the Construction Safety, Health & Welfare Regulations 2006 and the General Application Regulations 2007, and any other relevant statutory regulations and current amendments.
St Michaels House Lagan Rd Job Ref: 2009-001 Electrical O&M Manual SECTION 11 – AS INSTALLED DRAWINGS Contents: Lighting and Fire Alarm Services Power and General Services Intruder Alarm Services Electrical Schematics Alfa Electrical Ltd 29/01/2009