Operating instructions

Swim Spa Operators Guide
(XE) WIRING DIAGRAM - 14’, 16’, 18’
THE DIAGRAM IS INTENDED FOR THE XE PACK SYSTEM
Wiring Requirements
• 2-Hots, 1-Neutral, 1-Isolated Ground
• 0-40’ length, 4 Wire #6 AWG minimum 75˚C copper conductor
• Over 40’ length, 4 Wire #6 AWG minimum 75˚C copper conductor
(Check your local Electrical codes for 60 Amp
GFCI circuits for correct wire size for some areas vary)
Factory Recommended G.F.C.I. Load Center Wiring
L1
L2
N
G
The XM Pack require 230volts for operation
TV Lift control
Wiring Requirements:
• 2-Hots, 1-Neutral, 1-Isolated Ground
• 0-40 length, 4 Wire #6 AWG copper conductor
Over 40 length, 4 Wire #4 AWG copper conductor
Note: The white neutral wire from the back of the GFCI MUST be
connected to an incoming line neutral. The internal mechanism of
the GFCI requires this neutral connection. The GFCI will not work
without it.
ATTENTION!
IMPROPER WIRING WILL VOID WARRANTY
(Whit
e Wire
T
o the Spa)
l i a t g i P e t i h W
White Pigtail
Neutral Bar
r a B l a r t u e N
a p S m o r F e t i h W
Spa
To:
(Check your local Electrical codes for 60 Amp GFI circuits
for correct wire size for some areas varry)
P1
P2
P1
P1
P1
L1
L2
N
G
Pump 1 & 2
Circ. pump
or Blower
12 Volt Power supply
Ozonator
L1
L2
N
G
230 Volt 60 Hz / most common
120 Volt 60 Hz / Select models w/120volt pump and heater set to 120volts
L1
L2
N
G
230 Volt 50 Hz 2x16 circuits
L1
L2
N
G
230 Volt 50 Hz 1x32 circuit
L1
L2
N
G
The XM Pack require 230volts for operation
TV Lift control
Wiring Requirements:
• 2-Hots, 1-Neutral, 1-Isolated Ground
• 0-40 length, 4 Wire #6 AWG copper conductor
Over 40 length, 4 Wire #4 AWG copper conductor
Note: The white neutral wire from the back of the GFCI MUST be
connected to an incoming line neutral. The internal mechanism of
the GFCI requires this neutral connection. The GFCI will not work
without it.
ATTENTION!
IMPROPER WIRING WILL VOID WARRANTY
(
White Wire
To the Spa)
l i a t g i P e t i h W
Whi
te Pigtail
Neutral Bar
r a B l a r t u e N
a p S m o r F e t i h W
Spa
To:
(Check your local Electrical codes for 60 Amp GFI circuits
for correct wire size for some areas varry)
P1
P2
P1
P1
P1
L1
L2
N
G
Pump 1 & 2
Circ. pump
or Blower
12 Volt Power supply
Ozonator
L1
L2
N
G
230 Volt 60 Hz / most common
120 Volt 60 Hz / Select models w/120volt pump and heater set to 120volts
L1
L2
N
G
230 Volt 50 Hz 2x16 circuits
L1
L2
N
G
230 Volt 50 Hz 1x32 circuit
For Swim spa Wiring
Conguration please
refer to page 23 or
equipment pack for
detailed information
Note: Connection order may vary by pack model, please refer to equipment pack panel
for proper connection order.
Note: The white neutral wire from the back of the GFCI MUST be connected to an incoming
line neutral. The internal mechanism of the GFCI requires this neutral connection. The
GFCI will not work without it.
NOTE!
NOTE!