Power Requirements and Installation—Excluding North America and Japan
D-6
POWER REQUIREMENTS AND INSTALLATION—EXCLUDING NORTH AMERICA AND
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
JAPAN
The model 200ip/250ip dynamometer (excluding North America and Japan) requires
a dedicated wall receptacle which must be wired for operation and is included with
the dyno or may be shipped in advanced in a separate package. The dyno is equipped
with a ten foot power cord with a three-pin IEC plug pre-wired on the end. The
power cord is located at the front of the dyno, but is shipped inside of the dyno. Refer
to Figure 1-1 for the location of the power cord and page 1-23 for instructions on
routing the power cord.
The model 200ip/250ip dynamometer requires a dedicated 240VAC single phase
power outlet rated for 30A for proper operation. Failure to follow these
instructions could result in personal injury or damage to the dyno. Connecting
the dyno to the incorrect voltage will void the dyno warranty. Contact Dynojet with
any questions.
The dedicated wall receptacle is a three-pin IEC grounded 30A type and must be
wired in accordance with local building codes and requirements. Installation may
require a licensed electrician to conform to applicable safety standards.
If you are installing your dyno in a location other than North America or Japan
and the dyno is not equipped with a three pin IEC grounded plug, contact
Dynojet before attempting to connect the dyno.
Local and national electrical codes will require that the box containing the receptacle
is grounded.
This circuit should have a dedicated 30A double pole circuit breaker.
The dyno should be the only device connected to this circuit.
It may be necessary to install a delayed trip breaker due to the inrush current
drawn by the high pressure blowers.