Datasheet

64
v3.1 / Modification rights reserved
EE10EE10
Measured values
Relative Humidity
Working range 0...95 % RH
Accuracy
1)
at 20 °C (68 °F) and U
V
=24 V DC
Analogue (0-10 V, 4-20 mA) ±2 % RH (40...60 % RH) ±3 % RH (10...90 % RH)
Digital (RS485) ±3 % RH (30...70 % RH) ±5 % RH (10...90 % RH)
Temperature dependence typical 0.06 % RH /°C
(0.03 % RH / °F)
Temperature
Accuracy
1)
at 20 °C (68 °F) and U
V
=24 V DC output A3: ±0.25 °C (±0.45 °F) output A6: ±0.4 °C (±0.72 °F)
output J3: ±0.3 °C (±0.54 °F)
Output
Analogue 0-10 V -1 mA < I
L
< 1 mA
(RH: 0...100 % RH / T: see ordering guide) 4-20 mA (two wires) R
L
< (U
V
-10)/0.02 < 500 Ohm
Digital Interface RS485 with max. 32 devices on one bus
Protocol Modbus RTU or BACnet MS/TP
Temperature passive please see ordering guide
General
Voltage supply (U
V
)
0 - 10 V 15 - 40 V DC or 24 V AC ±20%
4 - 20 mA 10 + 0.02 x R
L
<
U
V
<
28 V DC (R
L
< 500 Ohm)
RS485 15 - 35 V DC or 24 V AC ±20%
Current consumption
Analogue (0-10 V, 4-20 mA) for DC supply: typ. 4 mA / for AC supply: typ. 15 mA
eff
Digital (RS485) for DC supply: typ. 9 mA / for AC supply: typ. 20 mA
eff
Electrical connection screw terminals max. 1.5 mm
2
(AWG 16)
Housing (polycarbonate) US Version: UL94V-0 approved / EU Version: UL94HB approved
Protection class IP30
Display for EE10-M1 Humidity / Temperature alternating
for EE10-M6 Humidity
CE compatibility according EN61326-1
EN61326-2-3
Temperature working range -5...55 °C
(23...131 °F)
Temperature storage range -25...60 °C (-13...140 °F)
1) Traceable to intern. standards, administrated by NIST, PTB, BEV...
The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2 (2-times standard deviation). The accuracy was calculated in accor -
dance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement).
EE10 is dedicated for accurate relative humidity (RH) and temperature (T)
measurement in residential and commercial HVAC.
The RH and T measured data is available either on two analogue outputs,
or on a BACnet or Modbus RTU interface. A version with analogue RH and
passive T output is also available. The measured data corresponding to the
active outputs can be read locally on the optional display.
Additional physical quantities are available on the Modbus RTU and BACnet
MS/TP interface: absolute humidity, mixing ratio, enthalpy, frost point tem-
perature and water vapor partial pressure.
The stylish enclosure is available in several colors and in two sizes
according to regional standards.
The back cover, which contains only the screw terminals, can be mounted
and wired first. The front cover containing the electronics can be simply
snapped onto the back cover right before commissioning. Thus the active
part of the device is not exposed to construction site pollution and can be replaced without tools within seconds.
EE10
Building automation
Indoor climate control
High accuracy and long term stability
Fast and easy installation
Modbus, BACnet or analogue outputs
Humidity and Temperature
Room Sensors
Typical Applications Features
Technical Data