PROPRIETARY DATA: This document contains proprietary data of ABB Inc. No disclosure, distribution (electronic or otherwise),
or other means of dissemination may be made without written permission.
3BUS 208 000 R1301170 Startup Options
Manual Startup
The following procedure involves manual intervention via the console keyboard
after reset has been initiated. It also enables reporting of conditions resulting in an
OFFLINE DEBUG status of the software.
1. Place the START MODE switch on the MPRC front panel to the STOP/DEBUG
position (down).
2. Either press the RESET switch on the MPRC front panel, or type reset on the
console keyboard (Scanning Platform window open).
3. For non-Ethernet MPRC Boards (086349-002):
When the console responds with OFFLINE DEBUG, enter a g {CR}.
For Ethernet MPRC Boards (086444-xxx):
When the console responds with OFFLINE DEBUG, place the START
MODE switch back to the center position, then enter a g {CR}.
4. The system will proceed with the startup and loading activity after about a 15-
second delay for diagnostic checks.
5. In less than a minute, the console should display the startup completion banner
which gives the download instructions from the Host computer. Execute the
PMMRLD command directed by the Host computer.
6. The Host computer download activity will result in three messages:
pmmFrame01: HOST TO AMS DOWNLOAD IN PROGRESS.
pmmFrame01: HOST TO AMS DOWNLOAD COMPLETED.
pmmFrame01: HOST COMMUNICATIONS ESTABLISHED.
If the download activity is not started, the console will eventually respond with:
pmmFrame01: HOST COMMUNICATIONS TIMEOUT.