3BUS 208 000 R130176 Platform Tuning
Alarms and Fault Reporting
Table 5-2 Motor Drive Alarms and Faults
Note: Faults (*) with a red blinking LED are reset by turning the power off
and on. Other faults are reset by pressing the START/STOP button.
Code Description
CF 0 - CF 9 Position of configuration switch S1.
Certain parameters can be modified only when S1=0.
AL 1 Parameter upload/download failed.
AL 2 Operation not allowed while start is active.
AL 3 Operation not allowed in remote or local control.
AL 4 REVERSE button disabled. Parameter 208 (Dir Lock) is active.
AL 5 Panel START button disabled.
DI configuration is three-wire and D12 is open.
AL 6 Operation not allowed. Parameter 503 (Param Lock) is active.
AL 10 Overcurrent controller active.
AL 11 Overvoltage controller active.
AL 12 Undervoltage controller active.
AL 13 Reserved. Contact supplier.
AL 14 Reverse command attempted in remote control (REM), while parameter 208
(Dir Lock) is active.
AL 15 - AL 16 Reserved. Contact supplier.
FL 1 Overcurrent:
Possible mechanical problem.
Acceleration and/or Deceleration times may be too small.
FL 2 DC overvoltage:
Input voltage too high.
Deceleration time may be too small.
FL 3 ACS 100 overtemperature:
Ambient temperature too high.
Severe overload.
FL 4 Fault current: output earth fault or short circuit
FL 5 Output overload.
FL 6 DC undervoltage.
FL 7 Analog input fault. See parameter 501.
FL 8 Motor overtemperature. See parameter 502.
FL 9 Panel disconnected from drive in local control.
NOTE: If FL9 is active when the power is turned off, the ACS 100 will start in
remote control (REM) when the power is turned back on.
FL 10 Parameters inconsistent.
Check that Al min (f
min
) is not greater than Al max (f
max
).
FL 11* DC bus ripple too large.
Check supply.
FL 12 Reserved. Contact supplier.
FL 13 - FL 19* Hardware error. Contact supplier.
Full display
blinking
Serial link failure.
Bad connection between the control panel and the ACS 100.