User manual

Page 9
EA Elektro-Automatik GmbH
Helmholtzstr. 31-33 • 41747 Viersen
Germany
Fon: +49 2162 / 3785-0
Fax: +49 2162 / 16230
www.elektroautomatik.de
ea1974@elektroautomatik.de
PS 5000 A Series
1.8.3 Specic technical data
160 W
Model
PS 5040-10 A PS 5080-05 A PS 5200-02 A
AC Input
Input voltage 90...264 V AC 90...264 V AC 90...264 V AC
Input connection 1ph,N,PE 1ph,N,PE 1ph,N,PE
Input frequency 50/60 Hz 50/60 Hz 50/60 Hz
Input fuse (internal) MT 4 A MT 4 A MT 4 A
Leak current < 3.5 mA < 3.5 mA < 3.5 mA
Power factor ~ 0.99 ~ 0.99 ~ 0.99
DC Output
Max. output voltage U
Max
40 V 80 V 200 V
Max. output current I
Max
10 A 5 A 2 A
Max. output power P
Max
160 W 160 W 160 W
Overvoltage protection range 0...44 V 0...88 V 0...220 V
Overcurrent protection range 0...11 A 0...5.5 A 0...2.2 A
Overpower protection range 0…176 W 0…176 W 0…176 W
TemperaturecoefcientforsetvaluesΔ/K Voltage / current: 100 ppm
Voltage regulation
Adjustment range 0...40.8 V 0...81.6 V 0...204 V
Accuracy
(1
(at 23 ± 5°C) < 0.1% U
Nom
< 0.1% U
Nom
< 0.1% U
Nom
Lineregulationat±10%ΔU
AC
< 0.02% U
Nom
< 0.02% U
Nom
< 0.02% U
Nom
Load regulation at 0...100% load < 0.05% U
Nom
< 0.05% U
Nom
< 0.05% U
Nom
Risetime10...90%ΔU Max. 30 ms Max. 30 ms Max. 30 ms
Display: Resolution See section „1.9.4.3. Resolution of the displayed values“
Display: Accuracy
(4
≤0.2%U
Nom
≤0.2%U
Nom
≤0.2%U
Nom
Ripple
(2
< 40 mV
PP
< 5 mV
RMS
< 80 mV
PP
< 10 mV
RMS
< 150 mV
PP
< 30 mV
RMS
Remote sensing compensation Max. 6% U
Nom
Max. 6% U
Nom
Max. 6% U
Nom
Current regulation
Adjustment range 0...10.2 A 0...5.1 A 0...2.04 A
Accuracy
(1
(at 23 ± 5°C) < 0.2% I
Nom
< 0.2% I
Nom
< 0.2% I
Nom
Lineregulationat±10%ΔU
AC
< 0.05% I
Nom
< 0.05% I
Nom
< 0.05% I
Nom
Loadregulationat0...100%ΔU
OUT
< 0.15% I
Nom
< 0.15% I
Nom
< 0.15% I
Nom
Ripple
(2
< 15 mA
RMS
< 7.5 mA
RMS
< 3 mA
RMS
Display: Resolution See section „1.9.4.3. Resolution of the displayed values“
Display: Accuracy
(4
≤0.2%I
Nom
≤0.2%I
Nom
≤0.2%I
Nom
Compensation 10%->90% load < 1.5 ms < 1.5 ms < 1.5 ms
Power regulation
Adjustment range 0…163.2 W 0…163.2 W 0…163.2 W
Accuracy
(1
(at 23 ± 5°C) < 1% P
Nom
< 1% P
Nom
< 1% P
Nom
Lineregulationat±10%ΔU
AC
< 0.05% P
Nom
< 0.05% P
Nom
< 0.05% P
Nom
Loadregulationat10-90%ΔU
OUT
*ΔI
OUT
< 0.75% P
Nom
< 0.75% P
Nom
< 0.75% P
Nom
Display: Resolution See section „1.9.4.3. Resolution of the displayed values“
Efciency
(3
~ 92% ~ 92% ~ 93%
(1Relatedtothenominalvalues,theaccuracydenesthemaximumdeviationbetweenanadjustedvaluesandthetrue(actual)value.
Example: a 80 V model has min. 0.1% voltage accuracy, that is 80 mV. When adjusting the voltage to 5 V, the actual value is allowed to differ max. 80 mV, which
means it might be between 4.92 V and 5.08 V.
(2 RMS value: LF 0...300 kHz, PP value: HF 0...20MHz
(3 Typical value at 100% output voltage and 100% power
(4 The display accuracy adds to the general accuracy, so the error (i.e. deviation) will be higher.