User manual

16
© 2006, Elektro-Automatik GmbH & Co. KG
Irrtümer und Änderungen vorbehalten
EN
© 2009, Elektro-Automatik GmbH & Co. KG
It either works in constant voltage or in constant current
operation (U-I characteristics).
This mode is suitable for parallel standby operation.
Overvoltage protection (OVP)
All models feature an overvoltage protection circuit
which is set 110% of the nominal output voltage. In
case of an overvoltage condition, whether caused by an
internal defect or by external reasons, the power output
is switched off and the error is indicated by ashing LED
„Error“ and also by pin 10 of the analogue interface.
After the OV condition is gone, the output can be swit-
ched on resp. the charging can be started again.
Overtemperature (OT)
All models also feature an internal temperature super-
vision. In case of overheating, the power output will
be temporarily switched off until the device has cooled
down, and then automatically switch on again. Charging
is thus only interrupted, but not stopped. The condition
is indicated by ashing LED „Error“ and by pin 10 of
the analogue interface.
Functional description
Errors
Any error is indicated by ashing LED „Error“. Following
error sources can be detected:
• Connection of a totally discharged battery
• Temperature sensor failure (broken wire etc.)
• Overvoltage (OVP)
• Overtemperature (OT)
The errors OVP and OT are also indicated at the ana-
logue interface.
Analogue interface
All models feature a 12 pin analogue interface on the
front of the device. It can be used to monitor the device
condition, as well as remotely start/stop the charging
procedure. Also see page 18.
BC 812-60R BC 824-40R BC 824-60R BC 848-40R
Mains input
Input voltage 90….264V 90….264V 90….264V 90….264V
Frequency 45….65Hz 45….65Hz 45….65Hz 45….65Hz
Power factor correction >0.99 >0.99 >0.99 >0.99
Input current at 230V 1.6A 1.6A 3.2A 3.2A
Input current at 100V 11.4A 11.4A 11.4A 11.4A
Fuse T16A T16A T16A T16A
Output - Voltage
Battery voltage U
Bat
12V 24V 24V 48V
Adjustable range 10….15V 20….30V 20….30V 40….60V
Stability at 10-90% load <0.05% <0.05% <0.05% <0.05%
Stability at ±10% ¨ U
In
<0.02% <0.02% <0.02% <0.02%
Ripple
<40mV
PP
<40mV
PP
<40mV
PP
<100mV
PP
Regulation 10-100% load <2ms <2ms <2ms <2ms
Output - Current
Nominal current 60A 40A 60A 40A
Stability at 0-100% ¨ U
Out
<0.15% <0.15% <0.15% <0.15%
Stability at ±10% ¨ U
In
<0.05% <0.05% <0.05% <0.05%
Ripple <100mAPP <100mAPP <100mAPP <100mAPP
Output - Power
Nominal power 960W 1000W 1500W 1500W
Nominal power at U
IN
<150V
960W 1000W 1000W 1000W
Miscellaneous
Operation temperature 0….40°C 0….40°C 0….40°C 0….40°C
Storage temperature -20….70°C -20….70°C -20….70°C -20….70°C
Humidity <80% <80% <80% <80%
Dimensions (WxHxD) 90x360x240mm 90x360x240mm 90x360x240mm 90x360x240mm
Weight 8.9kg 8.9kg 9.2kg 9.2kg
Article No. 27150317 27150318 27150319 27150320
Safety
EMC standards
Overvoltage category
Protection class
EN 60950
EN 61000-6-4, EN 61000-6-2, EN 550022 Klasse B
Class II
Class I
Technical specications