User manual
9
© 2014, Elektro-Automatik GmbH & Co. KG
EN
Technical description
Error output PF (Power Fail)
If a power fail error occurs (e.g. mains blackout ) this
open collector output will be pulled to GND via a 1kOhm
resistor. After that, the output voltage V1 will still be
provided for at least 5ms. A limit of 30V DC and 20mA
on this output may be not exceeded.
Schematic diagram
4
16
8,10GND V1
+ V1
1 Kohm
PF
V
max 30V DC
max 20 mA
+ V
PSU
Technical specications Connections of H15 plug
EA-PS 800 19“ 80W
90...264V
45...65Hz
90...360V
>0.99
up to 89%
<23A by NTC
by VDR
>20ms
58W...96W
0...70°C
>45°C 2.1W/°C
>60°C 4W/°C
-40°C ... +85°C
90% max.
yes
EN 60950, IEC 950
yes
EN 61000-6-3
EN 61000-6-2
162mm x 8HP x 3HE
640g
AC input voltage
Frequency
DC input voltage
Power factor of PFC
Overall effiency
Input surge current limitation
Input voltage spike limitation
Backup time
Output power in dependency of type
Ambient temperature
Temperature vs. Power derating
- for natural convection
- for forced air 1m/s
Storage temperature
Relative humidity (no condensation)
Safety: CE marking according to
low voltage directive 73/23/EEG
Safety according to
EMC: CE marking according to
EMC directive 89/336/EEG
EMI conducted & radiated emission
EMI humidity
Dimensions (D x W x H)
Weight
Technical Data
Pin
PS800
Single
PS800
Double
PS800
Double 24V
PS800
Triple
4 +V1 +V1 +V1 +V1
6 +V1 +V1 +V1 +V1
8 GND V1 GND V1 GND V1 GND V1
10 GND V1 GND V1 GND V1 GND V1
12 + Sense + Sense + Sense + Sense
14 - Sense - Sense - Sense - Sense
16 Power fail Power fail Power fail Power fail
18 -------------- +V2
+V2
+V2
20 ASF (opt.) GND V2
+V2 (only S01)
GND V2/V3
22 -------------- -------------- GND V2 -V3
24 Extern off
Extern off / ASF
1
Extern off / ASF
1
Extern off / ASF
1
26 -------------- -------------- -------------- --------------
28 N N N N
30 L L L L
32 PE PE PE PE
1) Optional, also see page 8
4
8
12
16
20
24
28
32
6
10
14
18
22
26
30
ASF / GND V2, V3
AC input
and
AC filter
30
28
32
L
N
PE
Power factor
correction
(PFC)
4,6
12
8,10
14
16
18
20
22
24
+V1
+Sense
-Sense
GND V1
Extern off / ASF
+V2
-V3
Power fail
control
Power fail (PF)
DC/DC
Converter
Note about special version S01:
At this version, output V2 (24V) is addi-
tionally led out on pin 20, in order to gain
compatibility to other manufacturers.