Cut Sheet

6019 HE 6019HELS 6019HEL
CT Metering
Data subject to change without notice. Consult local utility for area acceptance. All dimensions are in inches.
CT Mounting Bases
Meter Mounting Equipment
77
Part/UPC Catalog Amp # of C.T. Service Phase / Neutral Conductors
Number Number Rating Provisions Type Access AIC Line Load
78205137750 6019 A 400 2 1Ø or 3Ø/3W OH/UG 10K Studs Studs
78205137755 6019 E 800 2 1Ø or 3Ø/3W OH/UG 10K Studs Studs
78205140822 6019 HA 400 2 1Ø or 3Ø/3W OH/UG 50K Studs Studs
78205108761 6019 HAL 400 2 1Ø or 3Ø/3W OH/UG 50K #4 - 600 MCM #4 - 600 MCM
78205111459 6019 HALS 400 2 1Ø or 3Ø/3W OH/UG 50K Studs #4 - 600 MCM
78205140826 6019 HE 800 2 1Ø or 3Ø/3W OH/UG 50K Studs Studs
78205108608 6019 HEL 800 2 1Ø or 3Ø/3W OH/UG 50K #4 - 600 MCM #4 - 600 MCM
78205111461 6019 HELS 800 2 1Ø or 3Ø/3W OH/UG 50K Studs #4 - 600 MCM
78205137760 6067 A 400 3 3Ø/4W OH/UG 10K Studs Studs
78205137765 6067 E 800 3 3Ø/4W OH/UG 10K Studs Studs
78205140776 6067 HA 400 3 3Ø/4W OH/UG 50K Studs Studs
78205108698 6067 HAL 400 3 3Ø/4W OH/UG 50K #4 - 600 MCM #4 - 600 MCM
78205111452 6067 HALS 400 3 3Ø/4W OH/UG 50K Studs #4 - 600 MCM
78205140780 6067 HEE 800 3 3Ø/4W OH/UG 50K Studs Studs
78205107177 6067 HEEL 800 3 3Ø/4W OH/UG 50K #4 - 600 MCM #4 - 600 MCM
78205111464 6067 HEELS 800 3 3Ø/4W OH/UG 50K Studs #4 - 600 MCM
Application
• For use with CT rated enclosures
• For use with ANSI C12.11 bar type
current transformers
Construction
• Bar mounts are
1
/2” studs on 1
3
/4
centers (line & load)
Standards
• UL 414 Listed
• ANSI C12.7
• EUSERC 328A (6019 stud/stud)
• EUSERC 328B (6019 lug/lug)
• EUSERC 329A (6067 stud/stud)
• EUSERC 329B (6067 lug/lug)
All lugs accept three (3) wires per phase/neutral