SPECIFICATIONS
Eaton 9170
+
UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality
98
Table 16. Model Specifications for Split-Phase Power Modules (ASY-0673)
Three-Slot Cabinet
Optional
Chargers
UPS
kVA/Watts
Input Current
(200V)*
Output Current
(100/200V, 110/220V, 120/240V)
Recommended
Input Service*
Heat
Dissipation
NA 3/2500 16A** 15A, 14A, 12.5A 25A 285W
(0.98 kBTU/hr)
Six-Slot Cabinet
CAUTION Do NOT install more than three power and/or battery charger modules in a 6-slot cabinet.
Optional
Chargers
UPS
kVA/Watts
Input Current
(200V)
Output Current
(100/200V, 110/220V, 120/240V)
Recommended
Input Service
Heat
Dissipation
0 3/2500 16A 15A, 14A, 12.5A 25A 285W
(0.98 kBTU/hr)
1 3/2500 32A 15A, 14A, 12.5A 40A 570W
(1.95 kBTU/hr)
2 3/2500 48A** 15A, 14A, 12.5A 60A 860W
(2.93 kBTU/hr)
0 6/5000 32A 30A, 28A, 25A 40A 570W
(1.95 kBTU/hr)
1 6/5000 48A** 30A, 28A, 25A 60A 860W
(2.93 kBTU/hr)
0 9/7500 48A** 45A, 42A, 37.5A 60A 860W
(2.93 kBTU/hr)
Nine- and Twelve-Slot Cabinet
CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.
Optional
Chargers
UPS
kVA/Watts
Input Current
(200V)
Output Current
(100/200V, 110/220V, 120/240V)
Recommended
Input Service
Heat
Dissipation
0 3/2500 16A 15A, 14A, 12.5A 25A 285W
(0.98 kBTU/hr)
1 3/2500 32A 15A, 14A, 12.5A 40A 570W
(1.95 kBTU/hr)
2 3/2500 48A 15A, 14A, 12.5A 60A 860W
(2.93 kBTU/hr)
* In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in
the system. For redundant power module operation (N+X), increase the input current rating by 2A for each additional
redundant power module.
** Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external
battery cabinet XXXXX-Model/Batt4.