- Eaton UPS User's Guide

SPECIFICATIONS
Eaton 9170
+
UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality
99
Table 16. Model Specifications for Split-Phase Power Modules (ASY-0673) (continued)
Nine- and Twelve-Slot Cabinet
CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.
Heat
Dissipation
Recommended
Input Service
Output Current
(100/200V, 110/220V, 120/240V)
Input Current
(200V)
UPS
kVA/Watts
Optional
Chargers
3 3/2500 64A 15A, 14A, 12.5A 80A 1145W
(3.90 kBTU/hr)
4 3/2500 80A 15A, 14A, 12.5A 100A 1430W
(4.88 kBTU/hr)
5 3/2500 96A 15A, 14A, 12.5A 125A 1720W
(5.85 kBTU/hr)
0 6/5000 32A 30A, 28A, 25A 40A 570W
(1.95 kBTU/hr)
1 6/5000 48A 30A, 28A, 25A 60A 860W
(2.93 kBTU/hr)
2 6/5000 64A 30A, 28A, 25A 80A 1145W
(3.90 kBTU/hr)
3 6/5000 80A 30A, 28A, 25A 100A 1430W
(4.88 kBTU/hr)
4 6/5000 96A 30A, 28A, 25A 125A 1720W
(5.85 kBTU/hr)
5 6/5000 102A** 30A, 28A, 25A 125A 1995W
(6.75 kBTU/hr)
0 9/7500 48A 45A, 42A, 37.5A 60A 860W
(2.93 kBTU/hr)
1 9/7500 64A 45A, 42A, 37.5A 80A 1145W
(3.90 kBTU/hr)
2 9/7500 80A 45A, 42A, 37.5A 100A 1430W
(4.88 kBTU/hr)
3 9/7500 96A 45A, 42A, 37.5A 125A 1720W
(5.85 kBTU/hr)
4 9/7500 102A** 45A, 42A, 37.5A 125A 1995W
(6.75 kBTU/hr)
* In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in
the system. For redundant power module operation (N+X), increase the input current rating by 2A for each additional
redundant power module.
** Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external
battery cabinet XXXXX-Model/Batt4.