- Eaton UPS User's Guide

SPECIFICATIONS
Eaton 9170
+
UPS (3–18 kVA) User's Guide S 164201393 Rev E www.eaton.com/powerquality
102
Table 17. Model Specifications for Universal Power Modules (XXXXX-Model/03 and ASY-0674) (continued)
Nine- and Twelve-Slot Cabinet
CAUTION Do NOT install more than seven power and/or battery charger modules in a 9- or 12-slot cabinet.
Heat
Dissipation
Recommended
Input Service
Output Current for
200/208/220/230/240V
Input Current for
200/208/220/230/240V
UPS
kVA/Watts
Optional
Chargers
2 3/2100 46/45.5/45/44.5/44A 15/14.5/14/13/12.5A 60A 860W
(2.93 kBTU/hr)
3 3/2100 62/61.5/61/60.5/60A 15/14.5/14/13/12.5A 80A 1145W
(3.90 kBTU/hr)
4 3/2100 78/77.5/77/76.5/76A 15/14.5/14/13/12.5A 100A 1430W
(4.88 kBTU/hr)
5 3/2100 94/93.5/93/92.5/92A 15/14.5/14/13/12.5A 125A 1720W
(5.85 kBTU/hr)
0 6/4200 28/27/26/25/24A 30/29/28/26/25A 40A 570W
(1.95 kBTU/hr)
1 6/4200 44/43/42/41/40A 30/29/28/26/25A 60A 860W
(2.93 kBTU/hr)
2 6/4200 60/59/58/57/56A 30/29/28/26/25A 80A 1145W
(3.90 kBTU/hr)
3 6/4200 76/75/74/73/72A 30/29/28/26/25A 100A 1430W
(4.88 kBTU/hr)
4 6/4200 92/91/90/89/88A 30/29/28/26/25A 125A 1720W
(5.85 kBTU/hr)
5 6/4200 102A** 30/29/28/26/25A 125A 1995W
(6.75 kBTU/hr)
0 9/6300 42/40.5/39/37.5/36A 45/43.5/42/39/37.5A 60A 860W
(2.93 kBTU/hr)
1 9/6300 58/56.5/55/53.5/52A 45/43.5/42/39/37.5A 80A 1145W
(3.90 kBTU/hr)
2 9/6300 74/72.5/71/69.5/68A 45/43.5/42/39/37.5A 100A 1430W
(4.88 kBTU/hr)
3 9/6300 90/88.5/87/85.5/84A 45/43.5/42/39/37.5A 125A 1720W
(5.85 kBTU/hr)
* In High-Efficiency and Bypass modes the input current equals the output current plus 2A for each power module in
the system. For redundant power module operation (N+X), increase the input current rating by 2A for each additional
redundant power module.
** Maximum current rating for the cabinet size. If an additional charger is desired, it must be installed in external
battery cabinet XXXXX-Model/Batt4.